ProtoNode Driver Manual (FS-8700-124) rev 6.doc Manual

Page 7 of 17

4.2.Client Side Connection Descriptions

Section Title

 

 

 

 

 

 

 

 

 

 

 

Connections

 

 

 

 

 

 

 

 

 

 

 

Column Title

 

 

Function

 

 

 

 

Legal Values

 

Port

 

 

Specify which port the device

 

 

P1-P8

 

 

 

 

 

is connected to the ProtoNode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Protocol

 

Specify protocol used

 

 

TOSHIBA_UPS, TOSH_UPS

 

Baud*

 

 

Specify baud rate

 

 

 

1200–9600, standard baud rates

 

 

 

 

 

 

only (Vendor limitation)

 

 

 

 

 

 

 

 

 

 

Parity*

 

 

Specify parity

 

 

 

Even

 

 

 

 

Data_Bits*

 

Specify data bits

 

 

7

 

 

 

 

Stop_Bits*

 

Specify stop bits

 

 

1

 

 

 

 

Handshaking*

 

Specify hardware handshaking

 

 

None

 

 

 

 

Poll _Delay*

 

Time between internal polls

 

 

0-32000 seconds, 0.05 seconds

 

Example

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

//

Client Side Connections

 

 

 

 

 

 

 

 

 

Connections

 

 

 

 

 

 

 

 

 

 

 

Port,

Protocol,

 

Baud,

Parity,

Handshaking,

Data_Bits

 

Poll_Delay

 

P1,

TOSH_UPS,

 

1200,

Even,

None,

 

 

 

7

 

0.100s

 

4.3.Client Side Node Descriptors

Section Title

 

 

 

 

 

 

 

Nodes

 

 

 

 

 

 

 

Column Title

 

 

Function

 

 

Legal Values

 

Node_Name

 

 

Provide name for node

 

 

Up to 32 alphanumeric characters

 

Node_ID

 

 

Modbus station address of

 

1

 

 

 

physical server node

 

 

 

 

 

 

 

 

 

Protocol

 

 

Specify protocol used

 

 

TOSH_UPS, TOSHIBA_UPS

 

Node_Type

 

 

The model of the TIC UPS

 

 

1600, 1800, 4200, G8000,

 

 

 

 

 

G8000MM, G9000

 

 

 

 

 

 

 

 

Connection

 

 

Specify which port the device is

 

 

P1-P81

 

 

 

 

connected to the ProtoNode

 

 

 

 

1Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available on specific hardware.