FS-8700-127 Hanning & Kahl HCS-R Manual

Page 16 of 17

The same data will be stored in a Loop based Data Array which will then have the last known data for each loop

Data Array Offset

Description

Current Data

 

0 - 18

Data bits ( 0 – 1)

19

Receipt ok ( 0 ), Disturbance ( 1 )

20

From Loop ( 0 ), On Loop ( 1 )

2nd (Previous) Data

 

21 – 39

Data bits ( 0 – 1)

40

Receipt ok ( 0 ), Disturbance ( 1 )

41

From Loop ( 0 ), On Loop ( 1 )

3rd (Prior to previous) Data

 

42 – 60

Data bits ( 0 – 1)

61

Receipt ok ( 0 ), Disturbance ( 1 )

62

From Loop ( 0 ), On Loop ( 1 )

Appendix A.2. 2. How Server expects Data:

The Server expects data in the following format in order to constitute its response to HCS-R Clients.

Appendix A.2.1.

Data_Type is Ana_Input or not specified

 

 

 

 

 

Data Array Offset

Description

 

0 - 18

Data bits ( 0 - 1 )

19Receipt ok ( 0 ), Disturbance ( 1 )

20From Loop ( 0 ), On Loop ( 1 )

21Loop Number (0,1,2,3)

Appendix A.2.2.

Data_Type is Digi_Input

 

 

 

 

 

 

Data Array Offset (say 0)

 

 

Description

 

0 - 18

 

Data bits ( 0 - 1 )

 

19

 

Receipt ok ( 0 ), Disturbance ( 1 )

 

20

 

From Loop ( 0 ), On Loop ( 1 )

 

 

 

2 bits for Loop Number

 

 

 

Offsets

 

 

 

 

21 22

 

 

21,22

 

0

0

–Loop 1

 

 

 

1

0

–Loop 2

 

 

 

0

1

–Loop 3

 

 

 

1

1

–Loop 4

.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.FieldServer.com Tel: 408 262-2299 Fax: 408-262-2269 Toll_Free: 888-509-1970 email: support@FieldServer.com