FS-8700-16 BACnet PTP Serial Driver Manual

Page 4 of 20

 

 

3.Hardware Connections

It is possible to connect a BACnet device to any of the eight RS-2323ports. These ports just need to be configured for BACnet in the configuration file.

Configure the PLC (or BCU) according to manufacturer’s instructions

DB9M

DB9F

RJ45 Connector

Connector

EIA232

RJ45 to

8917-03 WIRE LIST

FUNCTION

FROM

TO

COLOUR

RX

RJ45-01

DB9M-02

GREY

CTS

RJ45-02

DB9M08

BROWN

DSR

RJ45-03

DB9M-06

YELLOW

GND

RJ45-04

DB9M-05

GREEN

GND

RJ45-05

 

RED

DTR

RJ45-06

DB9M-04

BLACK

RTS

RJ45-07

DB9M-07

ORANGE

TX

RJ45-08

DB9M-03

BLUE

 

8917-02 WIRE LIST

 

 

 

 

 

FUNCTION

FROM

TO

COLOUR

Rx

RJ45-01

DB9F-03

WHITE

GND

RJ45-04

DB9F-05

GREEN

Tx

RJ45-08

DB9F-02

BLUE

(408)-262-2299

FIELDSERVER

BACNET PTP

CONNECTION DIAGRAM

BASE NAME:

 

 

DATE: 7/30/06

FILE NAME:

 

 

BY: MC

 

 

 

 

 

 

 

 

Note that connection to a Trane BCU requires the 8917-02 option.

3Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available on specific hardware.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll Free: 888-509-1970 email: support@fieldserver.com

Page 4
Image 4
FieldServer FS-8700-16 instruction manual Hardware Connections