FS-8700-16 BACnet PTP Serial Driver Manual

Page 10 of 20

 

 

5.2.Server Side Connection Descriptions

Section Title

 

 

 

 

 

 

 

 

Connections

 

 

 

 

 

 

 

 

Column Title

 

Function

 

Legal Values

 

Port

Port name

 

 

 

P1-P87

 

 

 

 

 

 

 

110;

300;

600;

1200;

Baud*

Specify baud rate

 

 

2400; 4800; 9600; 19200;

 

 

 

 

 

38400; 57600; 115000

Parity*

Specify parity

 

 

Odd, Even, None

 

Data_Bits*

Specify data bits

 

 

7, 8

 

 

 

Stop_Bits*

Specify stop bits

 

 

1,2

 

 

 

Protocol

Specify Protocol Used

 

 

BACnet_PTP

 

 

Example

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

// Server Side Connections

 

 

 

 

 

 

 

 

Connections

 

 

 

 

 

 

 

 

Port,

Baud,

Parity,

Data_Bits,

Stop_Bits,

Protocol

 

P1,

9600,

Even,

7,

1,

 

BACnet_PTP

5.3.Server Side Node Descriptors

Section Title

 

 

 

 

 

 

Nodes

 

 

 

 

 

 

Column Title

 

Function

 

Legal Values

Node_Name8

Provide name for node

Up

to

32

alphanumeric

 

 

 

characters

 

 

Node_ID

BACnet station address of physical Server

1 - 4194303

 

 

 

node

 

 

 

 

 

Protocol

Specify protocol used

BACnet_PTP

 

Example

 

 

 

 

 

 

 

 

 

 

 

 

// Server Side Nodes

 

 

 

 

 

Nodes

 

 

 

 

 

 

Node_Name,

 

Node_ID,

Protocol

 

 

Virtual_BCU_11,

11,

BACnet_PTP

 

 

 

 

 

 

 

 

7Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction

manual for details of the ports available on specific hardware.

8 When using the Trane Tracer Summit Workstation System, this name will appear as the object name

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll Free: 888-509-1970 email: support@fieldserver.com

Page 10
Image 10
FieldServer FS-8700-16 instruction manual Server Side Connection Descriptions