FS-8700-24 ControlNet Driver Manual

Page 10 of 12

4.3.4.Unscheduled Map Descriptor Example

The following Map Descriptor will read data from a PLC5.

//Server Side Map Descriptors

Map Descriptors

Map_Descriptor_Name, A1,

Data_Array_Name, Data_Array_Offset,

Function,

Node_Name, Block_Number,

PCCC_Type,

Address,

Length

DA_AI3,

0,

RDBC,

PLC5,

7,

SINT,

33,

5

Active Map Descriptor polls the PLC regularly (change to WRBC to write)

Remote Node

 

Offset into the file

name of the PLC

PLC 5 file number to

(N7:33)

to poll

 

read (N7:33)

 

 

 

The following Map Descriptor will send data to the card to allow other nodes to read the data contained in the FieldServer’s Data Array.

//Server Side Map Descriptors

Map Descriptors

Map_Descriptor_Name, A1,

Data_Array_Name, Data_Array_Offset,

Function,

Node_Name,

Block_Number,

PCCC_Type,

Address,

Length

DA_AI3,

0,

WRBC,

Local,

7,

SINT,

125,

5

Active Map Descriptor transfers the data to or from the card (change to RDBC to read data written by other nodes)

Node name whose MacId

 

 

matches the

PLC 5 emulated file

Offset into the file

System_Station_Address

number (7-39)

(N7:125)

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldServer.com

Page 10
Image 10
FieldServer FS-8700-24 Unscheduled Map Descriptor Example, Following Map Descriptor will read data from a PLC5