4.Configuring the FieldServer for Unscheduled ControlNet Access with PCCC messaging
For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration Manual. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer (See “.csv” sample files provided with the FieldServer).
This section documents and describes the parameters necessary for configuring the FieldServer to communicate with ControlNet devices using PCCC messaging. This transfer mechanism would be used to communicate between the FieldServer and
The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable the FieldServer for ControlNet communications, the driver independent FieldServer buffers need to be declared in the “Data Arrays” section, the FieldServer virtual node(s) needs to be declared in the “Nodes” section, and the data to be transferred needs to be mapped in the “Unscheduled Map Descriptors” section. Details on how to do this can be found below.
Note that in the tables, * indicates an optional parameter, with the bold legal value being the default.
4.1.Server Side Connection Descriptors
Section Title |
|
|
Connections |
|
|
Column Title | Function | Legal Values |
Adapter | Adapter Name | ControlNet |
Protocol | Specify protocol used | ControlNet |
Example
//Connections
Connections |
|
Adapter, | Protocol |
ControlNet, | ControlNet |