INSTALLER TABLE
NOTE: You must be in the User Configuration Menu to enter the Installer Menu. Press TIME FWD and TIME BACK at same time.
Step | Press Button(s) | Displayed (Factory Default) | Press | or | to select: | COMMENTS | See | ||
Page | |||||||||
|
|
|
|
|
|
|
| ||
1 | SET | TIME | HEAT PUMP |
| 2 OR 3 |
| Selects: | 4 | |
| and SET | DAY | (1) |
|
|
| 1. one compressor on Y1. |
| |
| (hold for approx. |
|
|
|
| 2. two compressors on Y1, Y2. |
| ||
| 3 seconds) |
|
|
|
| 3. one compressor on W1. |
| ||
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
| |
2 | TIME | FWD | ELECT HEAT FAN |
| OFF |
| Fan cycles with call for Emergency heat if ON. | 4 | |
|
|
| (ON) |
|
|
| Fan always cycles with pump stages. |
| |
|
|
|
|
|
|
|
|
| |
3 | TIME | FWD | SET CYCLE HEAT |
| 9 to 40 |
| Selects HEAT anticipation adjustment. | 4 | |
|
|
| (13) |
|
|
|
|
| |
|
|
|
|
|
|
|
|
| |
4 | TIME | FWD | SET CYCLE COOL |
| 9 to 40 |
| Selects COOL anticipation adjustment. | 4 | |
|
|
| (13) |
|
|
|
| ||
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
| |
5 | TIME | FWD | SET CYCLE AUX |
| 1 to 40 |
| Selects AUXILIARY stage anticipation adjustment. | 4 | |
|
|
| (06) |
|
|
|
| ||
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
| |||
6 | TIME | FWD | COOL FAN DELAY OFF | 0 to 127 seconds | Selects time delay for COOL fan OFF. | 6 | |||
|
|
| (00) |
|
|
|
| ||
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
| |||
7 | TIME | FWD | FAN DELAY ON | 1 to 30 seconds | Selects time delay for fan ON for compressor stages. | 6 | |||
|
|
| (01) |
|
|
|
|
| |
|
|
|
|
|
|
| |||
8 | TIME | FWD | HEAT FAN DELAY OFF | 0 to 127 seconds | Selects time delay for HEAT fan OFF in Emergency | 6 | |||
|
|
|
|
|
|
|
| ||
|
|
| (00) |
|
|
| mode only when ELECT HEAT FAN (Step 2) is ON. |
| |
|
|
|
|
|
|
|
|
| |
9 | TIME | FWD | PUMP |
| OFF |
| Fossil Fuel Kit Alternative option. Turns compressor | 6 | |
|
|
| (ON) |
|
|
| OFF if Auxiliary is ON for longer than one minute. |
| |
|
|
|
|
|
|
| (Heat Pump 1 & 2) |
| |
10 | TIME | FWD | COMP LOCK |
| ON |
| Selects compressor | 6 | |
|
|
| (OFF) |
|
|
| or OFF.* |
| |
|
|
|
|
|
|
|
|
| |
11 | TIME | FWD | ECON |
| ON |
| Economizer option. Long Y1 cycles for cooling | 6 | |
|
|
| (OFF) |
|
|
| with outdoor air |
| |
|
|
|
|
|
|
| |||
12 | TIME | FWD | Allows selection of HEAT, EMER and COOL or | 6 | |||||
|
|
| AUTO |
|
|
| HEAT, EMER, COOL and AUTO with SYSTEM |
| |
|
|
|
|
|
|
| button. |
| |
13 | TIME | FWD | REMT SEN A |
| ON |
| Selects Remote Sensor A (connected to SA) if ON. | 6 | |
|
|
| (OFF) |
|
|
|
|
| |
|
|
|
|
|
|
|
|
| |
14 | TIME | FWD | REMT SEN b |
| ON |
| Selects Remote Sensor B (connected to SB) if ON. | 6 | |
|
|
| (OFF) |
|
|
|
|
| |
|
|
|
|
|
|
|
|
| |
15 | TIME | FWD | REMT SEN C |
| ON |
| Selects Remote Sensor C (connected to SC) if ON. | 6 | |
|
|
| (OFF) |
|
|
|
|
| |
|
|
|
|
|
|
|
|
| |
16 | TIME | FWD | STAT SEN L |
| OFF |
| When OFF, disables local sensor if a remote sensor | 7 | |
|
|
| (ON) |
|
|
| is enabled. |
| |
|
|
|
|
|
|
|
| ||
| PROGRAM RUN |
|
|
|
| Returns to normal operation |
| ||
|
|
|
|
|
|
|
|
|
*NOTE: COMP LOCK OFF permanently defeats compressor lockout. You must turn this selection ON if you do not have a system that already provides compressor