White Rodgers 37-6186B specifications Installer Table, Step, Press Buttons, to select, Comments

Models: 37-6186B

1 8
Download 8 pages 5.18 Kb
Page 5
Image 5
INSTALLER TABLE

INSTALLER TABLE

NOTE: You must be in the User Configuration Menu to enter the Installer Menu. Press TIME FWD and TIME BACK at same time.

Step

Press Button(s)

Displayed (Factory Default)

Press

or

to select:

COMMENTS

See

Page

 

 

 

 

 

 

 

 

1

SET

TIME

HEAT PUMP

 

2 OR 3

 

Selects:

4

 

and SET

DAY

(1)

 

 

 

1. one compressor on Y1.

 

 

(hold for approx.

 

 

 

 

2. two compressors on Y1, Y2.

 

 

3 seconds)

 

 

 

 

3. one compressor on W1.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

TIME

FWD

ELECT HEAT FAN

 

OFF

 

Fan cycles with call for Emergency heat if ON.

4

 

 

 

(ON)

 

 

 

Fan always cycles with pump stages.

 

 

 

 

 

 

 

 

 

 

3

TIME

FWD

SET CYCLE HEAT

 

9 to 40

 

Selects HEAT anticipation adjustment.

4

 

 

 

(13)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

TIME

FWD

SET CYCLE COOL

 

9 to 40

 

Selects COOL anticipation adjustment.

4

 

 

 

(13)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

TIME

FWD

SET CYCLE AUX

 

1 to 40

 

Selects AUXILIARY stage anticipation adjustment.

4

 

 

 

(06)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

TIME

FWD

COOL FAN DELAY OFF

0 to 127 seconds

Selects time delay for COOL fan OFF.

6

 

 

 

(00)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

TIME

FWD

FAN DELAY ON

1 to 30 seconds

Selects time delay for fan ON for compressor stages.

6

 

 

 

(01)

 

 

 

 

 

 

 

 

 

 

 

 

8

TIME

FWD

HEAT FAN DELAY OFF

0 to 127 seconds

Selects time delay for HEAT fan OFF in Emergency

6

 

 

 

 

 

 

 

 

 

 

 

(00)

 

 

 

mode only when ELECT HEAT FAN (Step 2) is ON.

 

 

 

 

 

 

 

 

 

 

9

TIME

FWD

PUMP

 

OFF

 

Fossil Fuel Kit Alternative option. Turns compressor

6

 

 

 

(ON)

 

 

 

OFF if Auxiliary is ON for longer than one minute.

 

 

 

 

 

 

 

 

(Heat Pump 1 & 2)

 

10

TIME

FWD

COMP LOCK

 

ON

 

Selects compressor short-cycle protection enabled

6

 

 

 

(OFF)

 

 

 

or OFF.*

 

 

 

 

 

 

 

 

 

 

11

TIME

FWD

ECON

 

ON

 

Economizer option. Long Y1 cycles for cooling

6

 

 

 

(OFF)

 

 

 

with outdoor air

 

 

 

 

 

 

 

 

12

TIME

FWD

HEAT-EMER-OFF-COOL-

HEAT-EMER-OFF-COOL

Allows selection of HEAT, EMER and COOL or

6

 

 

 

AUTO

 

 

 

HEAT, EMER, COOL and AUTO with SYSTEM

 

 

 

 

 

 

 

 

button.

 

13

TIME

FWD

REMT SEN A

 

ON

 

Selects Remote Sensor A (connected to SA) if ON.

6

 

 

 

(OFF)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

14

TIME

FWD

REMT SEN b

 

ON

 

Selects Remote Sensor B (connected to SB) if ON.

6

 

 

 

(OFF)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15

TIME

FWD

REMT SEN C

 

ON

 

Selects Remote Sensor C (connected to SC) if ON.

6

 

 

 

(OFF)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

TIME

FWD

STAT SEN L

 

OFF

 

When OFF, disables local sensor if a remote sensor

7

 

 

 

(ON)

 

 

 

is enabled.

 

 

 

 

 

 

 

 

 

 

PROGRAM RUN

 

 

 

 

Returns to normal operation

 

 

 

 

 

 

 

 

 

 

*NOTE: COMP LOCK OFF permanently defeats compressor lockout. You must turn this selection ON if you do not have a system that already provides compressor short-cycle protection. Please see “Lockout Bypass Option” to temporarily override compressor lockout.

5

Page 5
Image 5
White Rodgers 37-6186B specifications Installer Table, Step, Press Buttons, to select, Comments