5.2. Server Side Connection Descriptors
Section Title
Connections
Column Title Function Legal Values
Port Specify which port the device is connected
to the FieldServer P1-P8
2
Baud* Specify baud rate 150, 300, 1200, 2400, 4800, 9600
(Vendor limitation)
Parity* Specify parity None (Vendor limitation)
Data_Bits* Specify data bits 8 (Vendor limitation)
Stop_Bits* Specify stop bits 1 (Vendor limitation)
Protocol Specify protocol used Secutron
Handshaking*
Specify hardware handshaking None
Example
// Server Side Connections
Connections
Port, Protocol, Baud, Parity, Handshaking
P1, Secutron, 9600, None, None
5.3. Server Side Node Descriptors
Section Title
Nodes
Column
Title Function Legal Values
Node_Name Provide name for Node Up to 32 alphanumeric
characters
Node_ID Generic Node ID unique to port. Also used as panel
number. 0-9
Protocol Specify protocol used Secutron
Port Port to which node belongs P1-P8
Example
// Server Side Nodes
Nodes
Node_Name, Node_ID, Protocol, Connection
Node_1, 1, Secutron, P1
2
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction