FS-8700-72 Secutron Manual Page 12 of 15
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserv er.com
Tel: (408) 262-2299 Fax: (408) 262-2269 Toll Free: 888-509-1970 email: support@fieldser ver.com
Appendix A. Advanced Topics Appendix A.1. Event Function or Condition Codes
When the Client driver receives an e vent from the panel, it stores the event’s function or condition
code in the Secutron_Type=function Map Descriptor’s Data Array at the device number’s off set,
Example:
Device=3 on Circuit=1 goes into alarm – the Panel reports an event with function code A (Decim al 65)
The Map Descriptor Secutron_Type=device, Secutron_Circuit=1 will set a bit and store the event
function code A (Decimal 65) at offset 3 in the Map Descriptors’ Data Array.
The Secutron_Type=device Map Descriptors will set a bit if any of the events listed below occur on
that circuit or zone. The bit will be cleared if the panel reports the event as cleared.
The full list of event function codes are:
ASCII value Decimal Meaning
A
65 Alarm
B 66 Bypass
C 67 Comlink
D 68 Duplicate Addressable Device
E 69 Maintenance Alert
G 71 Ground Fault
H 72 Hot Key Pressed
I 73 Illegal Addressable Device
J 74 Switch
M 77 Missing Addressable Device
N 78 Non-Fire/Non-Reporting
P 80 Pull Station Alarm
Q 81 Releaser Abort
R 82 Releaser Halt
S 83 Supervisory
T 84 Trouble or Parameter Change
U 85 Wrong Device Type
W 87 Waterflow Alarm