FieldServer FS-X25 Start-Up Guide Page 3 of 12
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com
1 EQUI PMEN T S ET- UP 1.1 Supp lied eq uipm ent
FS-X25 Series FieldServer.
loaded with Modbus RTU driver, SMT Ethernet driver and any other dri vers o rdered. A d efault
configuration file ha s already been loaded onto the FieldServer. Check the Driver Manual and th e
FieldServer Configuration Manual for further information on this file.
USB Flash Drive loaded with:
FS-X25 Series Start-up Guide
FieldServer Configuration Manual
FieldServer Utilities Manual
All FieldServer Driver Manuals
Support Utilities
Any additional folders related to special files configured for a specific FieldServer
Additional components as required - See Driver Manual Supplement for details
Accessories:
7-ft Cat5 cable with RJ45 connectors at both ends (Part # FS-8915-10)
Power Supply
1.2 Moun ting
The FS-X25 Series FieldServer is supplied with an accessory bag which allows selection of adhesive feet (for
standing on a shelf) or mounting plates for wall or panel mount. A DIN Rail Mounting Kit (P/N FS-8915-28) may be
ordered separately.
1.3 Wiri ng
5-30VDC must be connected to the terminal block
1.3. 1 Com pli ance wi th U L R egul ati ons
For UL compliance, the following instructions must be met when operating the FieldServer.
The units shall be powered by listed LPS or Class 2 power supply suited to the expected operating temperature
range.
The interconnecting power connector and power cable shall:
Comply with local electrical code.
Be suited to the expected operating temperature range.
Meet the current and voltage rating for the FieldServer/Net
Furthermore, the interconnecting power cable shall:
Be of length not exceeding 3.05m (118.3”)
Be constructed of materials rated VW-1 or FT-1 or better.
If the unit is to be installed in an operating environment with a temperature above 65 °C, it should be installed
in a Restricted Access Area requiring a key or a special tool to gain access
This device must not be connected to a LAN segment with outdoor wiring.