FieldServer FS-X25 Start-Up Guide Page 6 of 12
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com
3 CONN ECTI ON TO THE DEV ICE 3.1 Seri al C onn ecti on
A DB-9 cable should be connected between the Serial port on the F S-X25 and the serial port of the target serial
device.
The Serial 1 port can be c onfigured as either P1 (for RS-232 connection) or R1 (for RS-485 connection). Likew ise
the Serial 2 port can be configured as P2 or R2. Note that if a P1 and a R1 connection is declared, the one declared
second will cause a configuration error on the error screen.
Figure 1: Serial Connection Ports
3.1. 1 DB-9 Pin outs fo r RS -23 2 C onne cti on
Used to connect to DTE type devices.
Typical null modem connection. (Used when
Hardware RTS→CTS flow control is required).
“3 wire” null modem connec tion (Used when Hardware
RTS→CTS flow control is not required).
The cable used (serial cross-over cable) is available at any electronics retailer/distributor.
1
9
5
6