8-4. Auto Address Setting

Basic wiring diagram: Example (1)

• If link wiring is not used

(The inter-unit control wires are not connected to multiple refrigerant systems.) Indoor unit addresses can be set without operating the compressors.

No. 1 (main unit)

 

 

settings

No. of indoor units

 

System address

(10 units setting)

 

(S004)

 

 

(system 1 setting)

 

 

0

 

 

(S002)

(S003)

 

 

 

 

 

ON

ON

(S005)

 

 

 

 

 

 

No. 2 (sub unit)

 

1 2

OFF

ON

ON

 

 

 

settings

 

 

 

 

 

No. of

 

 

1 2

3

OFF

Unit

(S006)

 

Unit number

(S007)

 

outdoor

ON

ON

number

units (2 units

ON

 

setting

ON

 

setting

 

 

 

 

 

setting)

1 2 3

OFF

(Unit No. 1)

1

2 3

OFF

(Unit No. 2)

(S007)

ONON

1 2 3

OFF

Outdoor Unit

Unit

 

Unit

No. 1

Outdoor main/sub

No. 2

 

(Main)

(Sub)

 

 

control wiring

 

Inter-unit control wiring

 

Indoor Unit

1-1

1-2

1-3

 

1-10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Remote controller

 

 

Remote controller

 

 

 

 

 

 

 

 

 

 

 

 

 

cross-over wiring

Fig. 8-5

(1) Automatic Address Setting from the Outdoor Unit

 

 

1.

On the outdoor main unit control PCB, check that the system address rotary switch (S002) is set to “1” and that

 

the DIP switch (S003) is set to

ON

ON “0.” (These are the settings at the time of factory shipment.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

2

 

OFF

 

 

 

 

 

 

 

 

 

2.

To set the number of indoor units that are connected to the outdoor unit to 10, on the outdoor main unit control

 

PCB set the No. of indoor units DIP switch (S005) to

 

 

 

 

 

 

 

ON “1,” and set the rotary switch (S004) to “0.”

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 2 3

OFF

3.

To set the number of outdoor units, on the outdoor main unit control PCB set the No. of outdoor units DIP switch

 

 

 

 

ON (2 units), and set the unit No. DIP switch (S007) to

 

 

 

 

 

 

 

 

 

 

 

 

 

(S006) to ON

 

 

 

 

ON

 

 

 

 

 

(unit No. 1 – main).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

2

 

3

OFF

 

 

1

 

 

 

2

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

4.

On the No. 2 (sub) unit control PCB, set the unit No. switch (S007) to

 

 

 

 

 

 

 

 

(unit No. 2).

 

 

2

 

 

1

 

3

 

5.Turn ON the power to the indoor and outdoor units.

6.On the outdoor main unit control PCB, short-circuit the automatic address pin (CN100) for 1 second or longer, then release it.

(Communication for automatic address setting begins.)

*To cancel, again short-circuit the automatic address pin (CN100) for 1 second or longer, then release it.

The LED that indicates that automatic address setting is in progress turns OFF and the process is stopped. Be sure to perform automatic address setting again.

(Automatic address setting is completed when LEDs 1 and 2 on the outdoor main unit control PCB turn OFF.)

7.Operation from the remote controllers is now possible.

*To perform automatic address setting from the remote controller, perform steps 1 to 5, then use the remote controller and complete automatic address setting.

Refer to “Automatic Address Setting from the Remote Controller.”

87