3-27. Installing the Drain Piping

(1)Prepare standard hard PVC pipe (O.D. 1-1/4") for the drain and use the supplied drain socket to prevent water leaks. The PVC pipe must be purchased separately. When doing this, apply adhesive for the PVC pipe at the connection point.

(2)If connecting a drain joint (supplied) to the threaded drain port, first wrap the drain port threads with sealing tape, then connect the joint. (Fig. 3-105)

(3)After connecting the drain pipe securely, wrap insulator (field supply) around the pipe.

(4)Ensure the drain pipe has a downward gradient (1/100 or more) and prepare traps as indicated in Fig. 3-106.

(5)Also, in another part of the pipe arrangement, prepare traps with an inspection plug to clean dust or debris that may cause leaking of water. (Fig. 3-107)

D(6) After connecting the drain piping, slowly pour water into the drain pan to check that the water drains smoothly.

3-28. Caution for Ducting Work

This unit has high static pressure (applicable external stat- ic pressure Max. 0.68 – 0.88 in. WG. In the case of small pressure resistance (for instance, a short duct), install a damper for adjusting air flow volume as air flow volume / air flow noise increases.

If the air conditioner is to be installed in a room such as an office or meeting room which needs a low sound level, provide a supply and return noise absorption chamber with an acoustic liner.

Include an air filter (field supply) at the return duct.

Sealing tape

Drain pan

Drain joint (supplied)

Drain opening

(25A or 1-11/32"male screw)

Fig. 3-105

Downward gradient

Min. 1/100

Good

Not good

Fig. 3-106

Min. 3-15/16 in.

Min. 1-31/32 in.

Inspection plug

3-29. Indoor Fan Performance

How to Read the Diagram

The vertical axis is the External Static Pressure (in. WG) while the horizontal axis represents the Air Flow (CFM). The characteristic curve for the “H,” “Med,” and “Lo” fan speed control.

The nameplate values are shown based on the “H” air flow. Therefore in the case of 36 Type, the flow is 1059 CFM, while the External Static Pressure is 0.72 in. WG at “H” position. If the external static pressure is too great (due to long extension of duct, for example), the air flow volume may drop too low at each air outlet. (Fig. 3-108)

 

 

 

 

 

 

Fig. 3-107

 

 

 

 

(in. WG)

 

36 Type

 

 

(in. WG)

 

48 Type

 

1.00

 

 

 

 

 

1.00

line

 

 

 

 

 

 

 

 

 

Limit

 

 

 

 

 

line

 

 

 

 

 

 

 

0.80

Limit

 

 

 

0.80

 

 

 

 

 

 

 

 

 

 

 

Pressure

 

 

H

 

Pressure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H

 

 

 

M

 

 

 

M

 

 

 

 

 

 

 

 

 

0.60

 

 

 

 

0.60

 

L

 

 

L

 

 

 

 

 

Static

 

 

 

 

H

Static

 

 

 

 

 

 

 

 

 

 

 

 

 

External

0.40

 

 

 

 

External

0.40

 

 

 

 

 

 

 

 

 

 

 

H,M

 

0.20

 

 

 

M

 

0.20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

line

 

 

 

 

line

 

 

 

 

Limit

 

 

 

 

Limit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

883

1059

1236

 

0

 

 

 

 

 

 

 

1059

1236

1412

Air Flow (CFM)

Air Flow (CFM)

NOTE H: At shipment

Fig. 3-108

54

W-3WAY_ECO-i_US.indd 54

2008/02/07 10:56:00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 54
Image 54
Sanyo 85464369098000, XMHX1252, XMHX1852 Indoor Fan Performance How to Read the Diagram, Min -31/32 Inspection plug