2. SELECTING THE INSTALLATION SITE

2-1. Indoor Unit

AVOID:

areas where leakage of flammable gas may be expected.

places where large amounts of oil mist exist.

direct sunlight.

locations near heat sources which may affect the performance of the unit.

locations where external air may enter the room directly. This may cause “sweating” on the air discharge ports, causing them to spray or drip.

locations where the remote controller will be splashed with water or affected by dampness or humidity.

installing the remote controller behind curtains or furniture.

locations where high-frequency emissions are generated.

DO:

select an appropriate position from which every corner of the room can be uniformly cooled.

select a location where the ceiling is strong enough to support the weight of the unit.

select a location where tubing and drain pipe have the shortest run to the outdoor unit.

allow room for operation and maintenance as well as unrestricted air flow around the unit.

install the unit within the maximum elevation difference above or below the outdoor unit and within a total tubing length (L) from the outdoor unit as detailed in Table 1-9.

allow room for mounting the remote controller about 3 ft. off the floor, in an area that is not in direct sunlight nor in the flow of cool air from the indoor unit.

NOTE

Air delivery will be degraded if the distance from the floor to the ceiling is greater than 10 ft.

23

Ceiling-MountedType

Ceiling

Wall

Min. 10 in.

Min. 10 in.

Front view

NOTE

The rear of the indoor unit can be installed flush against the wall.

Air discharge

Min. 2 ft.

 

 

 

Air intake

 

 

 

 

 

 

 

 

 

 

 

 

 

Side view

Max. 10 in.

 

Obstacle

Fig. 2-1

Concealed Duct (High-Static Pressure)Type 4-Way Air Discharge Semi-Concealed Type

3 ft.

3 ft.

3 ft.

3 ft.

3 ft.

 

Fig. 2-2

1-Way Air Discharge Semi-Concealed Type

Ceiling

3 ft.

 

Min.

Min. 2 in.

 

Wall

Obstacle

Air

discharge Air

intake Wall

Min. 2 in.

Side view

Fig. 2-3

Wall-Mounted Type

Min.

Min.6 in.

Min.

6 in.

 

6 in.

Front View

Fig. 2-4