Table 1-13 Indoor Unit Tubing Connection Size ( 1 40)

 

 

 

in. (mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor unit type

7

9

 

12

18

24

36

48

Total system horsepower

0.8

1

 

1.3

2

3

4

5

Distribution

Suction tubing

 

 

 

 

ø5/8"

 

 

 

 

 

 

 

 

(ø15.88)

 

 

 

 

joint –

 

 

 

 

 

 

 

 

 

Discharge tubing

 

 

 

 

ø1/2"

 

 

 

 

solenoid valve

 

 

 

 

(ø12.70)

 

 

 

 

kit tubing

Liquid tubing

 

 

 

 

ø3/8"

 

 

 

 

 

 

 

 

 

(ø9.52)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Solenoid valve

Gas tubing

 

 

ø1/2"

 

 

 

ø5/8"

 

kit – Indoor

 

 

(ø12.70)

 

 

 

(ø15.88)

 

 

 

 

 

 

 

 

 

 

 

unit tubing

 

 

 

 

 

 

 

 

 

 

Liquid tubing

 

 

ø1/4"

 

 

 

ø3/8"

 

connection

 

 

 

 

 

 

 

 

(ø6.35)

 

 

 

(ø9.52)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*1: For the solenoid valve kits, use type 160 with parallel specifications. Branch the tubing before and after the solenoid valve kits.

1-7. Straight Equivalent Length of Joints

Design the tubing system by referring to the following table for the straight equivalent length of joints.

Table 1-14 Straight Equivalent Length of Joints

Gas tubing size (in.(mm))

1/2"

5/8"

3/4"

7/8"

1"

1-1/8"

1-1/4"

1-1/2"

 

(12.7)

(15.88)

(19.05)

(22.22)

(25.4)

(28.58)

(31.8)

(38.1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

90ooelbow

 

 

1 ft.

1.1 ft.

1.4 ft.

1.6 ft.

1.7 ft.

1.9 ft.

2.3 ft.

2.6 ft.

 

 

 

(0.30 m)

(0.35 m)

(0.42 m)

(0.48 m)

(0.52 m)

(0.57 m)

(0.70m)

(0.79 m)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

45ooelbow

 

 

0.8 ft.

0.9 ft.

1 ft.

1.2 ft.

1.3 ft.

1.4 ft.

1.7 ft.

1.9 ft.

 

 

(0.23 m)

(0.26 m)

(0.32 m)

(0.36 m)

(0.39 m)

(0.43 m)

(0.53 m)

(0.59 m)

 

 

 

U-shape tube bent

 

 

3 ft.

3.4 ft.

4.1 ft.

4.7 ft.

5.1 ft.

5.6 ft.

6.9 ft.

7.8 ft.

(R2–23/64–3–15/16 in.)

 

 

(0.90 m)

(1.05 m)

(1.26 m)

(1.44 m)

(1.56 m)

(1.71 m)

(2.10 m)

(2.37 m)

 

 

 

 

 

 

 

 

 

 

 

 

Trap bend

 

 

7.5 ft.

9.2 ft.

10.5 ft.

12.5 ft.

14.1 ft.

15.4 ft.

16.4 ft.

14.0 ft.

 

 

(2.30 m)

(2.80 m)

(3.20 m)

(3.80 m)

(4.30 m)

(4.70 m)

(5.00 m)

(5.80 m)

 

 

 

Y-branch distribution joint

 

 

 

 

Equivalent length conversion not needed.

 

 

Ball valve for service

Equivalent length conversion not needed.

Table 1-15 Refrigerant tubing (Existing tubing can be used.)

Tubing size (in. (mm))

Material O

 

Material 1/2H • H

 

 

 

 

 

ø1/4" (ø6.35)

 

t1/32 (t0.8)

 

 

 

 

 

 

 

ø3/8" (ø9.52)

 

t1/32 (t0.8)

ø1-1/8" (ø28.58)

t5/128 (t1.0)

 

 

 

 

 

ø1/2" (ø12.7)

 

t1/32 (t0.8)

ø1-1/4" (ø31.75)

t3/64 (t1.1)

 

 

 

 

 

ø5/8" (ø15.88)

 

t5/128 (t1.0)

ø1-1/2" (ø38.10)

over t3/64 (t1.15)

 

 

 

 

ø3/4" (ø19.05)

over t5/128 (t1.0)

ø1-5/8" (ø41.28)

over t3/64 (t1.20)

 

 

 

 

 

ø7/8" (ø22.22)

 

t5/128 (t1.0)

 

 

 

 

 

 

 

*When bending the tubes, use a bending radius that is at least 4 times the outer diameter of the tubes.

In addition, take sufficient care to avoid crushing or damaging the tubes when bending them.

1-8. Additional Refrigerant Charge

Additional refrigerant charge amount is calculated from the liquid tubing total length as follows.

Table 1-16-1 Amount of Refrigerant Charge Per ft., According to Liquid Tubing Size

Liquid tubing

ø1/4"

ø3/8"

ø1/2"

ø5/8"

ø3/4"

ø7/8"

size

(ø6.35)

(ø9.52)

(ø12.7)

(ø15.88)

(ø19.05)

(ø22.22)

Amount of

 

 

 

 

 

 

refrigerant

0.279

0.602

1.38

1.99

2.78

3.93

charge (oz/ft.)

 

 

 

 

 

 

Required amount of charge = Necessary Amount of Refrigerant Charge Per Unit (14053 Type) + (Amount of refrigerant charge per ft. of each size of liquid tube

its tube length) + (...) + (...)

*Always charge accurately using a scale for weighing.

Table 1-16-2 Necessary Amount of Refrigerant Charge Per Unit

CHDZ09053

CHDZ14053

CHDZR09053

CHDZR14053

113 oz/unit

13

W-3WAY_ECO-i_US.indd 13

2008/02/15 12:29:03

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 13
Image 13
Sanyo CHDZR14053, XMHX1252, XMHX1852, CHDZR09053, 85464369098000 Refrigerant tubing Existing tubing can be used