CAUTION

Be careful since the fan will start when you

short the pin on the indoor control board.

 

 

(4)When the check of drainage is complete, open the check pin (CHK) and remount the insulator and drain cap onto the drain inspection port.

3-24. Increasing the Fan Speed

If external static pressure is too great (due to long extension of ducts, for example), the air flow volume may drop too low at each air outlet. This problem may be solved by increasing the fan speed using the following procedure:

(1)Remove 4 screws on the electrical component box and remove the cover plate.

(2)Disconnect the fan motor sockets in the box.

(3)Take out the booster cable (sockets at both ends) clamped in the box.

Power supply outlet

Inter-unit control wiring

Fig. 3-97

U

 

 

 

(4)Securely connect the booster cable sockets between the disconnected fan motor sockets in step 2 as shown in Fig. 3-98.

(5)Place the cable neatly in the box and reinstall the cover plate.

Electrical component box

Booster cable

 

Fan

Booster cable

motor

Fan motor socket

 

(At shipment)

(Booster cable installed)

Fig. 3-98

How to read the diagram

Indoor Fan Performance

(in. WG)

 

7, 12 Type

Pressure

0.60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.40

 

 

line

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Static

 

Limit

 

line

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Limit

 

 

 

 

HT

 

External

 

 

 

 

 

 

 

 

0.20

 

 

 

 

 

 

H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M

 

 

 

 

 

 

 

 

 

 

L

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

177

 

353

 

 

 

Air Flow (CFM)

(in. WG)

 

18 Type

 

 

 

 

 

 

0.60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pressure

 

 

line

 

 

 

 

 

 

 

 

 

 

 

0.40

 

Limit

 

 

 

 

 

 

 

 

 

 

 

Static

 

 

 

line

 

 

 

 

Limit

 

 

 

 

External

0.20

 

H

 

 

 

 

 

 

 

 

 

 

HT

 

 

 

 

 

 

 

M

L

0

353530

Air Flow (CFM)

The vertical axis is the external static pressure (in. WG) while the horizontal axis represents the air flow (CFM). The characteristic curves for “HT,” “H,” “M” and “L” fan speed control are shown. The nameplate values are shown based on the “H” air flow. For the 24 type, the air flow is 635 CFM, while the external static pressure is

0.20in. WG at “H” position. If external static pressure is too great (due to long extension of ducts, for example), the air flow volume may drop too low at each air out- let. This problem may be solved by increasing the fan speed as explained above.

(in. WG) 0.60

PressureStatic

0.40

 

External

0.20

 

 

0

24 Type

line

 

 

Limit

 

 

Limit

line

HT

 

 

 

 

 

H

 

 

M

 

 

L

353

 

706

Air Flow (CFM)

(in. WG)

0.60

PressureStatic

0.40

 

External

0.20

 

 

0

36 Type

Limit

line

 

Limit

line

HT

 

 

H

M

L

706 1059 Air Flow (CFM)

NOTE HT: Using the booster cable

H:At shipment

Fig. 3-99