3-32. Duct for Fresh Air

There is a duct connection port (knock-out hole) at the right- rear of the top panel of the indoor unit for drawing in fresh air. If it is necessary to draw in fresh air, remove the cover by opening the hole and connecting the duct to the indoor unit through the connection port. (Fig. 3-126)

3-33. Shaping the Tubing

The positions of the refrigerant tubing connections are shown in the figure below. (The tubing can be routed in 3 directions.)

*When routing the tubing out through the top or right sides, knock out the appropriate parts in the top panel and cut notches in the side panel as shown in Fig. 3-111.

*When routing the tubing out through the top, the optional L-shape tubing kit is required.

T

Rear outlet port

Inter-unit control wiring

(ø1-3/16", knock-out, use rubber grommet)

Outside air intake duct connection port (ø3-15/16", knock-out)

Power supply outlet (ø1-3/16", knock-out)

Rear tubing hole

Left-side drain hose outlet port

Fig. 3-126

If the tubing is to be routed out together, use a box cutter or simi- lar tool to cut out the part of the rear cover indicated by the marked area in the figure below, to match the positions of the tubes. Then draw out the tubing.

Rear cover

Fig. 3-127

3-34. Installing the Drain Piping

Prepare standard PVC pipe for the drain and connect it to the indoor unit drain pipe with the supplied hose clamps to prevent water leaks.

(1) Drain hose connection

The drain hose is connected below the refrigerant tubing.

(2) Installing the drain hose

To install the drain hose, first place 1 of the 2 hose bands over the unit drain port and the other hose band over the hard PVC pipe (not supplied). Then connect both ends of the supplied drain hose.

On the unit drain side, grasp the hose band with pliers and insert the drain hose all the way to the base.

If other commercially available hose bands are used, the drain hose may become pinched or wrinkled and there is danger of water leakage. Therefore be sure to use the supplied hose bands. When sliding the hose bands, be careful to avoid scratching the drain hose.

Do not use adhesive when connecting the supplied drain hose to the drain port (either on the main unit or the PVC pipe).

Wrap the hose with the supplied drain hose insulation and use the 4 twist ties so that the hose is insulated with no gaps.

Connect the drain piping so that it slopes downward from the unit to the outside. (Fig. 3-129)

Fig. 3-128

Downward gradient

Min. 1/100

Good

Not good

Fig. 3-129

CAUTION

Attach so that the hose band fastener is on the side of the drain port. (Fig. 3-130)

Attach the hose bands so that each is approximately 13/64 – 63/64 in. from the end of the supplied drain hose.

58

W-3WAY_ECO-i_US.indd 58

2008/02/07 10:56:02

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 58
Image 58
Sanyo CHDZR14053, XMHX1252, XMHX1852 Duct for Fresh Air, Shaping the Tubing, Rear cover, Downward gradient Min /100