Always check the gas density WARNING limit for the room in which the

unit is installed.

1-11. Check of Limit Density

When installing an air conditioner in a room, it is necessary to ensure that even if the refrigerant gas accidentally leaks out, its density does not exceed the limit level for that room. If the density could exceed the limit level, it is necessary to provide an opening between the unit and the adjacent room, or to install mechanical ventilation which is interlocked with a leak detector.

(Total refrigerant charged amount: oz)

(Min. indoor volume where the indoor unit is installed: ft.3)

<Limit density 0.3 (oz/ft.3)

The limit density of refrigerant which is used in this unit is 0.3 oz/ft.3 (ISO 5149).

The shipped outdoor unit comes charged with the amount of refrigerant fixed for each type, so add it to the amount that is charged in the field. (For the refrigerant charge amount at shipment, refer to the unit’s nameplate.)

1-12. Installing Distribution Joint

Pay special attention to any CAUTION location, such as a basement,

etc., where leaking refrigerant can accumulate, since refrig- erant gas is heavier than air.

(1)Refer to “HOW TO ATTACH DISTRIBUTION JOINT” enclosed with the optional distribution joint kit (APR-CHRZP900BAB, RZP224BAB, RZP680BAB, RZP1350BAB).

(2)When creating a branch using a commercially available T-joint (header joint system), orient the main tubing so that it is either horizontal (level) or vertical. In order to prevent accumulation of refrigerant oil in stopped units, if the main tubing is horizontal then each branch tubing length should be at an angle that is greater than horizon- tal. If the main tubing is vertical, provide a raised starting portion for each branch.

[Header joint system]

Be sure to solidly weld shut the T-joint end (marked by “X” in the figure). In addition, pay attention to the insertion depth of each connected tube so that the flow of refrigerant within the T-joint is not impeded.

When using the header joint system, do not make fur- ther branches in the tubing.

Do not use the header joint system on the outdoor unit side.

(3)If there are height differences between indoor units or if branch tubing that follows a distribution joint is connect- ed to only 1 unit, a trap or ball valve must be added to that distribution joint. (When adding the ball valve, locate it within 15 - 3/4" of the distribution joint.)

If a trap or ball valve is not added, do not operate the system before repairs to a malfunctioning unit are completed. (The refrigerant oil sent through the

15

tubing to the malfunctioning unit will accumulate and may damage the compressor.)

Minimum indoor volume & floor area as against the amount of refrigerant is roughly as given in the follow- ing table.

 

ft.3

 

 

 

 

 

 

 

 

 

 

 

 

 

ft.2

 

 

 

10000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1136

 

 

indoorMin.volume

9500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1079

indoorMin.floor area

ceilingthe(whenis 8.8 ft. high)

 

 

 

 

 

the density

limit of

 

 

2000

 

 

 

 

 

 

 

227

 

9000

 

Range below

 

 

 

 

 

 

 

 

 

1022

 

 

 

8500

 

the density limit of

 

 

 

 

 

 

 

966

 

 

 

8000

 

0.3 oz/ft.3

 

 

 

 

 

 

 

 

 

909

 

 

 

7500

 

 

 

 

 

 

 

 

 

 

852

 

 

 

7000

 

(countermeasures

 

 

 

 

 

 

 

795

 

 

 

6500

 

not needed)

 

 

 

 

 

 

 

 

 

738

 

 

 

6000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

682

 

 

 

5500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

625

 

 

 

5000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

568

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

511

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

454

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

398

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3000

 

 

 

 

 

Range above

 

 

 

 

 

341

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2500

 

 

 

 

 

 

 

 

 

 

284

 

 

 

 

 

 

 

 

0.3 oz/ft.3

 

 

 

 

 

 

 

 

1500

 

 

 

 

 

 

 

 

 

 

170

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1000

 

 

 

 

 

(countermeasures

 

 

114

 

 

 

 

 

 

 

 

 

 

 

 

 

500

 

 

 

 

 

needed)

 

 

 

 

 

57

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

500

1000

1500

2000

2500

3000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

oz

 

 

Total amount of refrigerant

Tube branching methods (horizontal use)

 

 

 

 

 

B

 

 

A

Horizontal

A

 

B

line

View as seen

 

 

 

 

 

 

 

 

 

from arrow

 

 

Arrow view

 

 

Header joint system (Indoor)

 

 

Install at a

 

 

 

 

 

positive angle

 

 

Outdoor

 

Indoor

 

 

 

 

 

 

 

 

 

 

 

 

 

Install at a

Indoor

 

 

 

 

positive angle

 

 

 

 

(15 – 30°)

 

 

 

 

 

Horizontal

 

 

 

 

line

 

 

 

 

 

 

 

Indoor

 

 

 

L3

6.56 ft.

Horizontal

Solidly welded

 

 

line

 

shut (X)

 

 

 

 

Types of vertical trap specifications

(When using ball valve)

 

 

Main tubing

 

 

 

 

Ball valve

Indoor unit (more than 2 units)

(If only 1 unit is connected, a ball valve

(BV: purchased

separately)

is also needed on this side.)

Indoor unit (1)

 

 

 

 

(When not using ball valve)

 

Main tubing

 

Horizontal

 

 

 

 

 

 

 

 

Indoor unit

(Each unit is connected

Branch tubing is

 

to tubing that is either

 

level or is directed

directed upward.

 

 

downward.)

 

More than

 

 

 

 

 

 

7–7/8"

 

 

 

Indoor unit is directed downward

 

 

 

W-3WAY_ECO-i_US.indd 15

2008/02/07 10:55:40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 15
Image 15
Sanyo XMHX1252, XMHX1852, CHDZR09053, CHDZR14053 Tube branching methods horizontal use, Header joint system Indoor