Sanyo CHDZR09053, XMHX1252 Display during automatic address setting, LED 2, Blink alternately

Models: XMHX1852 CHDZR09053 XMHX1252 85464369098000 CHDZR14053

1 106
Download 106 pages 6.26 Kb
Page 92
Image 92

Display during automatic address setting

On outdoor main unit PCB

LED 2 1

* Do not short-circuit the automatic address setting pin (CN100) again while automatic address set-

 

ting is in progress. Doing so will cancel the setting operation and will cause LEDs 1 and 2 to turn

Blink alternately

OFF.

 

*When automatic address setting has been successfully completed, both LEDs 1 and 2 turn OFF.

*LED 1 is D72. LED 2 is D75.

*If automatic address setting is not completed successfully, refer to the table below and correct the problem. Then perform automatic address setting again.

Display details of LEDs 1 and 2 on the outdoor unit control PCB

(: ON : Blinking : OFF)

LED 1

LED 2

Display meaning

 

 

After the power is turned ON (and automatic address setting is not in progress), no communication with the indoor

 

 

units in that system is possible.

 

 

After the power is turned ON (and automatic address setting is not in progress), 1 or more indoor units are

 

 

confirmed in that system; however, the number of indoor units does not match the number that was set.

Alternating

Automatic address setting is in progress.

 

 

 

Automatic address setting completed.

 

 

At time of automatic address setting, the number of indoor units did not match the number that was set.

Simultaneous

“ ” (when indoor units are operating) indication appears on the display.

Alternating

Refer to “Table of Self-Diagnostic Functions and Description of Alarm Displays.”

 

Note: ” indicates that the solenoid is fused or that there is a CT detection current failure (current is detected when the compressor is OFF).

Remote controller display

is blinking

92

W-3WAY_ECO-i_US.indd 92

2008/02/07 10:56:14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 92
Image 92
Sanyo CHDZR09053, XMHX1252, XMHX1852, CHDZR14053 Display during automatic address setting, LED 2, Blink alternately