6-3. Insulating the Refrigerant Tubing

Tubing Insulation

Thermal insulation must be applied to all unit tubing, including the distribution joint (purchased separately). (Fig. 6-7)

*For gas tubing, the insulation material must be heat resistant to 248°F or above. For other tubing, it must be heat resistant to 176°F or above.

Insulation material thickness must be 25/64 in. or greater.

If the conditions inside the ceiling exceed DB 86°F and RH 70%, increase the thickness of the gas tub- ing insulation material by 1 step.

If the exterior of the outdoor unit CAUTION valves has been finished with a

square duct covering, make sure you allow sufficient space to use the valves and to allow the panels to be attached and removed.

Taping the flare nuts

Wind the white insulation tape around the flare nuts at the gas tube connections. Then cover up the tubing con- nections with the flare insulator, and fill the gap at the union with the supplied black insulation tape. Finally, fasten the insulator at both ends with the supplied vinyl clamps. (Fig. 6-8)

Insulation material

The material used for insulation must have good insula- tion characteristics, be easy to use, be age resistant, and must not easily absorb moisture.

Two tubes arranged together

Liquid tubing

Gas tubing

Insulation

Three tubes arranged together

 

Cosmetic

 

 

(finishing) tape

Gas tubing

 

 

 

 

Liquid tubing

 

Insulation

Balance tubing

Four tubes arranged together

Cosmetic

 

(finishing) tape

Suction tubing

 

Discharge tubing

 

Balance tubing

 

Insulation

Liquid tubing

Fig. 6-7

Sealer (supplied)

 

Insulation tape (white)

 

(supplied)

 

Flare insulator (supplied)

Unit side

Tube insulator

(not supplied)

insulator

Heat resistant

 

248°F or above

CAUTION

After a tube has been insulated,

never try to bend it into a narrow curve because it can cause the tube to break or crack.

Flare nut

Vinyl clamps (supplied)

 

 

Fig. 6-8

 

Refrigerant tubing and insulator

Drain insulator

(not supplied)

Drain pipe and insulator

and clamp.

Large

(not supplied)

(supplied)

 

Packing

 

clamp.

Insulation

Small

tape

hose band

Vinyl

(supplied)

Flare clamp

 

 

insulator

 

Seal

The procedure used for installing the insulator for both gas and liquid tubes are the same.

Fig. 6-9

Never grasp the drain or refrigerant connecting outlets

when moving the unit.