Table 1-17 Refrigerant Charge Amount at Shipment (for outdoor unit)

DC

CHDZ09053

CHDZ14053

CHDZR09053

CHDZR14053

(oz)

 

 

416

416

 

 

 

 

1-9. System Limitations

Table 1-18 System Limitations

Max. No. allowable connected outdoor units

2

 

 

Max. capacity allowable connected outdoor units

307,100 BTU/h (32 hp, 90 kw)

 

 

Max. connectable indoor units

40 *1

Max. allowable indoor/outdoor capacity ratio

50 – 130 %

 

 

*1: In the case of 20 hp (type 191.100 BTU/h) or smaller units, the number is limited by the total capacity of the connected indoor units.

1-10. Installation Standards

Relationship between A/C units and refrigerant tubing

Outdoor unit

4-tube layout

Outdoor unit

3-tube layout

Solenoid

2-tube layout

Indoor unit

 

 

valve kit

 

 

Suction tube

 

Suction tube

Gas tube

 

 

 

 

 

 

Discharge tube

 

Discharge tube

 

Liquid tube

 

 

Liquid tube

 

Liquid tube

 

 

 

 

Balance tube

 

 

 

 

 

Install the solenoid valve kit 98 ft. or less from the indoor unit.

In quiet locations such as hospitals, libraries, and hotel rooms, the refrigerant noise may be somewhat notice- able. It is recommended that the solenoid valve kit be installed inside the corridor ceiling, at a location outside the room.

Room

Indoor unit

YES

Hallway

Room

NO

Room

Indoor unit

Indoor unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hallway

Solenoid valve kit

Room

Indoor unit

Solenoid valve kit

Common solenoid valve kit

Multiple indoor units under group control can utilize a solenoid valve kit in common.

Categories of connected indoor unit capacities are determined by the solenoid valve kit.

Type of solenoid valve kit

Total capacity of indoor units (BTU/h)

 

 

160

19.000 < Total capacity < 54.600

 

 

56

7.500 < Total capacity < 19.000

 

 

If the capacity range is exceeded, use 2 solenoid valves connected in parallel.

14

W-3WAY_ECO-i_US.indd 14

2008/02/07 10:55:40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 14
Image 14
Sanyo 85464369098000 Refrigerant Charge Amount at Shipment for outdoor unit, System Limitations 18 System Limitations