3-19-3. Wiring the ceiling panel

(1)Loosen the 2 screws on the electrical component box lid, and remove the lid. (Fig. 3-80)

(2)Fasten the wiring connector (7P, red) which comes out from the ceiling panel using the lead wire clamps (2 locations) on the unit. Then connect it to the connector (7P, red) inside the indoor unit electrical component box. (Fig. 3-81)

If the connector is not connected, “P09” is displayed on the remote controller, and the automatic flap will not operate. Be sure to securely connect the connec- tor.

Check that the wiring connector is not pinched between the electrical component box and the lid.

Check that the wiring connector is not pinched between the indoor unit and the ceiling panel.

3-19-4. Installing the side panel and intake grille

A. Installing the side panel

(1)Grasp the side panel finger grip and slide the panel in the direction of the arrow to install the side panel. (Fig. 3-82)

(2)Fasten the side panel onto the ceiling panel using the supplied screws (4 12 or 5/32" 15/32").

B. Installing the intake grille

To install the intake grille, follow the procedure for removing it in the reverse order. (Fig. 3-83)

When installing the intake grille, be careful that the flap lead wire does not become pinched. (Fig. 3-83)

3-19-5. Others

A. Check after installation

Check again that there is no gap between the indoor

unit and the ceiling panel, or between the ceiling

panel and the ceiling surface.

Screws

Electrical component

A

 

 

box cover

 

Fig. 3-80

Electrical component box

Inter-unit control wiring

 

Indoor unit connector

Power supply outlet

Fig. 3-81

 

Tabs

Fasten with screws

 

(4 ss12 or 5/32" ss15/32")

Tab

Slide

Slide the side panel so that the side panel tabs are fastened to the ceiling panel. Then fasten in place with the supplied screws

(4 ss12 or 5/32" ss15/32").

* If there is a gap, then water leakage and condensa-

tion may occur.

Check that the wiring connections are secure.

* If the wiring is not connected, the automatic flap will

not operate. (“P09” is displayed on the remote

controller.) In addition, water leakage,

condensation, and other problems may occur.

B. If a wireless remote controller is used

For details concerning the installation procedure, refer to the installation manual which was supplied with the optional wireless remote controller and indoor unit internal receiver.

Screw

Fig. 3-82

Screw

Fig. 3-83

47

W-3WAY_ECO-i_US.indd 47

2008/02/07 10:55:58

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 47
Image 47
Sanyo CHDZR09053, XMHX1252, XMHX1852, CHDZR14053 Installing the side panel and intake grille, Installing the intake grille