Sanyo 85464369098000 Test Run Procedure, Items to Check Before the Test Run, Unit with the unit

Models: XMHX1852 CHDZR09053 XMHX1252 85464369098000 CHDZR14053

1 106
Download 106 pages 6.26 Kb
Page 84
Image 84

8-2. Test Run Procedure

<Outdoor unit control PCB> Unit No. setting switch (S007)

<Outdoor unit control PCB> Unit No. setting switch (S006)

<Outdoor unit control PCB> Unit No. setting switch (S004 and S005)

(Check the link wiring.)

<Outdoor unit control PCB> Unit No. setting switch (S002 and S003)

Recheck the items to check before the test run.

NO

Have the outdoor sub units been connected?

YES

*1 *1 The unit with the unit

Set the unit address.No. set to 1 is the

main unit. All other units are sub units.

Set the No. of outdoor units.

Set the No. of indoor units.

 

Are the inter-unit control wires

NO

CASE 1

connected to more than 1 refrigerant

 

 

 

system?

 

 

 

 

YES

 

 

 

 

 

 

 

Set the system address.

 

 

 

 

 

 

 

Items to Check Before the Test Run

1.Turn the remote power switch on at least 5 hours before the test, in order to energize the crank case heater.

2.Turn the outdoor service valves (4 locations) to the full-open positions.

Use caution when making the settings. If there are duplicated system addresses, or if the settings for the Nos. of the indoor units are not consistent, an alarm will occur and the system will not start.

These settings are not made on the indoor unit PCB.

 

When multiple outdoor main units exist, disconnect the terminals

Note: It is not necessary to remove

Refer to Fig. 8-4

extended from the shorted plugs (CN003) at all outdoor main unit

the socket that is used to

 

PCBs except for 1.

short-circuit the terminal plugs

 

Alternatively, move the sockets to the OPEN side.

from the outdoor sub unit

 

 

 

PCBs.

 

 

 

 

 

 

Is it possible to turn ON the power only

 

YES

 

CASE 2

 

 

 

 

 

 

for the 1 refrigerant system where the

 

 

 

 

 

 

 

 

 

 

 

 

 

test run will be performed?

 

 

 

 

 

 

 

 

 

 

Turn ON the indoor and

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

outdoor unit power for that

 

 

 

 

 

 

 

 

 

 

 

 

 

 

refrigerant system only.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Will automatic address setting be

 

 

 

 

 

Make necessary corrections.

 

 

 

 

 

 

 

 

 

 

Short-circuit the automatic address pin (CN100)

 

NO

performed in Heating mode?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

on the outdoor main unit PCB for 1 second or

 

 

 

 

 

 

 

 

 

 

 

 

 

 

longer, then release it.

 

CASE 3B

 

YES

CASE 3A

 

 

Turn OFF the indoor and

 

 

 

 

 

 

 

 

 

 

 

 

 

outdoor unit power.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is it OK to start the compressors?

Is it OK to start the compressors?

 

 

 

 

 

 

 

 

 

LED 1 and 2 blink alternately

 

 

 

 

 

Check the alarm contents.

 

(about 2 or 3 minutes).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Turn ON the indoor and

Turn ON the indoor and

 

 

 

 

 

 

 

 

NO

 

 

 

outdoor unit power.

outdoor unit power.

 

 

 

 

 

 

 

 

 

Are LEDs 1 and 2 on the

*2

 

*2

 

 

 

Make necessary

 

 

 

 

 

outdoor unit PCB OFF?

Short-circuit the mode change pin

Short-circuit the automatic address

 

corrections

 

 

Refer to “Table of

 

 

 

 

 

 

 

(CN101) on the outdoor main unit PCB.

pin (CN100) on the outdoor main

 

 

 

 

 

 

Self-Diagnostic Functions and

 

 

 

 

 

 

 

 

Description of Alarm Displays.”

 

YES

At the same time, short-circuit the

unit PCB for 1 second or longer,

 

 

 

 

 

 

 

 

Turn OFF the indoor

 

 

 

 

 

automatic address pin (CN100) for 1

then release it.

 

and outdoor unit power.

 

 

 

 

second or longer, then release it.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*3

 

*3

Start indoor and outdoor unit

Start indoor and outdoor unit

cooling operation.

heating operation.

LED 1 and 2 blink alternately.

LED 1 and 2 blink alternately.

Check the alarm

contents.

Are LEDs 1 and 2 on the

NO

outdoor unit PCB OFF?

 

YES

*2 A minimum of 5 hours must have passed after the power was turned ON to the outdoor unit.

*3 All indoor units operate in all refrigerant systems where the power is ON.

Check that test run preparation is OK.

(Do not allow the short-circuited pins to remain short-circuited.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Set the wired remote controller for test run.

 

 

 

 

 

 

 

 

 

Refer to the remote

 

 

NO

Check and make corrections according to

 

 

controller test-run

 

 

settings.

Does system operate?

“Table of Self-Diagnostic Functions.”

 

 

 

 

 

 

 

 

 

YES

Return remote control to normal mode

End test run.

Fig. 8-3

84

W-3WAY_ECO-i_US.indd 84

2008/02/07 10:56:11

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 84
Image 84
Sanyo 85464369098000, XMHX1252, XMHX1852 Test Run Procedure, Items to Check Before the Test Run, Unit with the unit