Sanyo 85464369098000 How to Attach the Corner & Air-Intake Grille, Checking After Installation

Models: XMHX1852 CHDZR09053 XMHX1252 85464369098000 CHDZR14053

1 106
Download 106 pages 6.26 Kb
Page 39
Image 39
Locations of air-intake grille hinges

3-13-4. How to Attach the Corner & Air-Intake Grille

Attaching the corner cover and air-intake grille

A. Attaching the corner cover

(1)Check that the safety cord from the corner cover is fastened to the ceiling panel pin, as shown in the fig- ure. (Fig. 3-49)

(2)Use the supplied screws to attach the corner cover to the ceiling panel.

Pin

XM

Fig. 3-49

Place the corner cover so that the 3 tabs fit into the holes in the ceiling panel.

Then fasten it in place with the supplied screws.

B. Attaching the air-intake grille

To install the air-intake grille, follow the steps for Removing the grille in the reverse order. By rotating the air-intake grille, it is possible to attach the grille onto the ceiling panel from any of 4 directions. Coordinate the directions of the air-intake grilles when installing multiple units, and change the directions according to customer requests. (Fig. 3-50)

When attaching the air-intake grille, be careful that the flap lead wire does not become caught.

Be sure to attach the safety cord that prevents the air- intake grille from dropping off to the ceiling panel unit as shown in the figure at right.

With this ceiling panel, the directions of the air-intake grille lattices when installing multiple units, and the position of the label showing the company name on the corner panel, can be changed according to customer requests, as shown in the figure below. However, the optional wireless receiver kit can only be installed at the refrigerant-tubing corner of the

ceiling unit. (Fig. 3-51)

Refrigerant tube side

Optional wireless receiver kit

* Only this area is possible for installation.

Electrical component box for power PCB

Hole for ceiling panel hook

Hook that prevents the grille from dropping

*The grille can be installed with these hinges facing in any of 4 directions.

Drain pipe side

Fig. 3-50

Can be installed rotated 90°

Fig. 3-51

Electrical component box for control PCB

3-13-5. Checking After Installation

Check that there are no gaps between the unit and the ceiling panel, or between the ceiling panel and the ceiling surface. Gaps may cause water leakage and condensation.

Check that the wiring is securely connected.

If it is not securely connected, the auto flap will not operate. (“P09” is displayed on the remote controller.) In addition, water leak- age and condensation may occur.

3-13-6. When Removing the Ceiling Panel for Servicing

When removing the ceiling panel for servicing, remove the air-intake grille and air filter, disconnect the wiring connector inside the electrical component box, and then remove the 4 mounting screws.

3-13-7. Adjusting the Auto Flap

The air-direction louver on the ceiling panel outlet can be adjusted as follows.

Adjust the louver to the desired angle using the remote controller. The louver also has an automatic air-sweeping mechanism.

NOTE

Never attempt to move the louver by hand.

Proper air flow depends on the location of the air conditioner, the layout of the room and furniture, etc. If cooling or heating seems

inadequate, try changing the direction of the air flow.

39