1-5. Tubing Length

Select the installation location so that the length and size of refrigerant tubing are within the allowable range shown

in the figure below.

1.

 

Main tubing length LM = LA + LB … b 262 ft.

 

 

2.

 

Main distribution tubes LC – LH are selected according to the capacity after the

 

 

 

 

 

distribution joint.

 

3.

 

Sizes of indoor unit connection tubing 1 – 40 are determined by the connection tubing

 

 

 

 

 

sizes on the indoor units.

H3 C

 

L2

 

LM

L1

 

 

 

B

 

 

 

T-joint tubing

 

 

 

Balance tubing

LB

LC

LD

LE

(header joint system)

 

 

(ø9.52)

L3

 

 

 

 

 

 

 

 

 

 

 

 

LA

 

 

 

 

 

 

 

 

 

 

4

5

6

7

40

H1

 

 

 

 

Explanation of symbols

LF

For

 

 

 

 

 

 

extension

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Max. 1.3 ft.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Distribution joint

 

 

 

 

 

 

 

 

 

 

 

 

For

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

extension

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(APR: purchased separately)

 

Max. 1.3 ft.

 

 

 

 

 

 

 

 

 

 

Solenoid valve kit

H2

 

 

 

 

 

 

 

 

 

LH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ball valve (field supply)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T-joint (field supply)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LG

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Solidly welded shut

 

L4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R410A distribution joint

 

 

 

 

 

 

(pinch weld)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

APR-CHRZP900BAB (for outdoor unit)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note: Do not use commercially available T-joints for the liquid tubing

 

 

 

and  parts.

 

 

APR-RZP224BAB (for indoor unit)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

APR-RZP680BAB (for indoor unit)

* Be sure to use special R410A distribution joints (APR: purchased separately) for outdoor

 

 

APR-RZP1350BAB (for indoor unit)

 

unit connections and tubing branches.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 1-9 Ranges that Apply to Refrigerant Tubing Lengths and to Differences in Installation Heights

Item

Mark

 

Contents

 

L1

 

Max. tubing length

 

Actual length

 

 

 

 

 

 

Equivalent length

 

 

 

 

 

 

∃∃L (L2 – L4)

 

Difference between max. length and min.

 

 

length from the No. 1 distribution joint

 

 

 

Allowable tubing

LM

 

Max. length of main tubing (at max. diameter)

length

 

1, 2... 40

 

Max. length of each distribution tube

 

 

 

L1+ 1+ 2 ... 39

+

Total max. tubing length including length of

A+B+LF+LG+LH each distribution tube (only liquid tubing)

 

L5

Distance between outdoor units

 

H1

When outdoor unit is installed higher than indoor unit

Allowable elevation

When outdoor unit is installed lower than indoor unit

 

difference

H2

Max. difference between indoor units

 

H3

Max. difference between outdoor units

Allowable length of

L3

T-joint tubing (field-supply); Max. tubing length between

joint tubing

the first T-joint and solidly welded-shut end point

 

L = Length, H = Height

NOTE

Length (ft.)

>

492

 

>

574

 

>

131

 

>

262*2

>

98

 

>

984

 

>

32

 

>

164

>

131

 

>

49

>

13

 

>

6.6

1:If the longest tubing length (L1) exceeds 295 ft. (equivalent length), increase the sizes of the main tubes (LM) by 1 rank for the discharge tubes, suction tubes, and liquid tubes. (Use a field supply reducer.)

2:If the longest main tube length (LM) exceeds 164 ft., increase the main tube size at the portion before 164 ft. by 1 rank for the suction tubes and discharge tubes. (Use a field supply reducer.)

(For the portion that exceeds 164 ft., set based on the main tube sizes (LA) listed in the table on the following page.)

11

W-3WAY_ECO-i_US.indd 11

2008/02/07 10:55:39

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 11