Possible cause of malfunction

 

Alarm

 

message

 

 

 

 

 

 

 

Activation of

Protective device in indoor unit

Thermal protector in indoor unit fan motor is activated.

<<P01>>

protective

is activated.

Improper wiring connections of ceiling panel.

<<P09>>

device

 

Float switch is activated.

<<P10>>

 

Protective device in outdoor

Incorrect discharge temperature. (Comp. No. 1)

P03

 

unit is activated.

 

 

 

High pressure switch or over load relay is activated.

P04

 

 

 

 

Power supply voltage is unusual. (The voltage is less than 160 V

 

 

between L1 and L2 phase.)

 

 

 

Negative (defective) phase.

P05

 

 

O2 sensor (detects low oxygen level) activated

P14

 

 

 

 

 

 

Compressor running failure resulting from missing phase in the

P16

 

 

compressor wiring, etc. (Start failure not caused by IPM or no gas.)

 

 

 

 

 

 

 

 

 

Incorrect discharge temperature. (Comp. No. 2)

P17

 

 

 

 

 

 

Compressor 3 discharge temp. failure

P18

 

 

Outdoor unit fan motor is unusual.

P22

 

 

Overcurrent at time of compressor runs more than 80Hz (DCCT

P26

 

 

secondary current or ACCT primary current is detected at a time

 

 

other than when IPM has tripped.)

 

 

 

IPM trip (IPM current or temperature)

H31

 

 

 

 

 

 

Inverter for compressor is unusual. (DC compressor does not

P29

 

 

operate.)

 

 

 

 

 

 

 

Thermistor

Indoor thermistor is either open

Indoor coil temp. sensor (E1)

<<F01>>

fault

or damaged.

Indoor coil temp. sensor (E2)

<<F02>>

 

 

Indoor coil temp. sensor (E3)

<<F03>>

 

 

Indoor suction air (room) temp. sensor (TA)

<<F10>>

 

 

 

 

 

 

Indoor discharge air temp. sensor (BL)

<<F11>>

 

Outdoor thermistor is either

Comp. No. 1 discharge gas temp. sensor (DISCH1)

F04

 

open or damaged.

Comp. No. 2 discharge gas temp. sensor (DISCH2)

F05

 

 

Outdoor No. 1 coil gas temp. sensor (EXG1)

F06

 

 

 

 

 

 

Outdoor No. 1 coil liquid temp. sensor (EXL1)

F07

 

 

 

 

 

 

Outdoor air temp. sensor (AIR TEMP)

F08

 

 

Compressor intake port temperature sensor (RDT)

F12

 

 

High pressure sensor. Negative (defective) N phase.

F16

 

 

Low-pressure sensor failure

F17

 

 

 

 

 

 

Compressor 3 discharge temp. sensor failure (DISCH3)

F22

 

 

 

 

 

 

Outdoor No. 2 coil gas temp. sensor (EXG2)

F23

 

 

 

 

 

 

Outdoor No. 2 coil liquid temp. sensor (EXL2)

F24

 

 

 

 

 

 

Outdoor No. 3 coil gas temp. sensor (EXG3)

F25

 

 

 

 

 

 

Outdoor No. 3 coil liquid temp. sensor (EXL3)

F26

 

 

 

 

EEP ROM on indoor unit P.C.B. failure

 

F29

 

 

 

 

Protective

Protective device for compressor

EEP ROM on the main or sub outdoor unit PCB has failed.

F31

device for

No. 1 is activated.

Overload current is detected.

H01

 

compressor is

 

 

 

 

Lock current is detected.

H02

activated

 

 

 

 

Current is not detected when comp. No. 1 is ON.

H03

 

 

 

Protective device for compressor

Compressor No. 2 current trouble (overcurrent)

H11

 

No. 2 is activated.

Compressor No. 2 current trouble (locked)

H12

 

 

Compressor No. 2 CT sensor disconnected or short circuit

H13

 

 

Compressor No. 2 discharge temp. sensor disconnected

H15

 

 

 

 

 

Protective device for compressor

Compressor No. 3 current trouble (overcurrent)

H21

 

No. 3 is activated.

Compressor No. 3 current trouble (locked)

H22

 

 

Compressor No. 3 CT sensor disconnected or short circuit

H23

 

 

 

 

 

 

Compressor No. 3 discharge temp. sensor disconnected

H25

 

 

Low pressure switch is activated.

H06

 

 

 

 

 

Oil sensor fault.

Comp. No. 1 oil sensor

H08

 

(Disconnection, etc.)

Comp. No. 2 oil sensor

H27

 

 

Comp. No. 3 oil sensor

H28