3-15. Placing the Unit Inside the Ceiling

CAUTION

Be sure to use a level gauge

and confirm that the unit is

 

 

 

level. If it is not level, water

 

leakage may occur.

(1)Use the supplied M5 or 3/16" screws (4) to attach the full-size installation diagram to the indoor unit suspension lugs, in order to obtain the ceiling opening dimensions for suspending the unit. (Fig. 3-56)

Caution: Piping and wiring work must be performed inside the ceiling after the unit is suspended. Therefore if the ceiling is already installed, the wiring and piping work should be completed up to the connection points prior to suspending the unit.

(2)Attach the special washers (supplied) and nuts (field supply) to the suspension bolts (4 locations).

CAUTION

Use M10 or 3/8" nuts.

The length of the suspension bolts must be such that

there is a space of at least 19/32 in. below the bottom

of the suspension lugs, as shown in Fig. 3-56. If the

length of the suspension bolts is too long, the bolts

may interfere with the ceiling panel and louver motor,

Full-scale installation diagram

Suspension lug

 

 

 

 

 

 

 

25/32 – 1 in.

over 19/32 in.

 

 

Fig. 3-56

A

For fresh air intake

 

(ø3-15/16 hole) A

3-5/32

 

6-11/16

Unit: in.

Fig. 3-57

6-11/16

For fresh air intake

(ø3-15/16 hole) A

 

8-1/16

Unit: in.

Fig. 3-58

preventing their installation.

(3)

Thread the 3 hexagonal nuts and 2 washers (field

 

supply) onto each of the 4 suspension bolts as

 

shown in Fig. 3-59. Use 1 nut and 1 washer for the

 

upper side, and 2 nuts and 1 washer for the lower

 

side, so that the unit will not fall off the suspension

 

lugs.

(4)

Lift up the indoor unit and fit the suspension bolts

 

into the notches in the suspension lugs.

Nuts and washers (Used above and below.)

Double nuts

over 19/32 in.

Suspension bolt

Suspension lug

Notch

25/32-1 in.

(5) Adjust so that the distance between the bottom of

the indoor unit suspension lugs and the bottom of

the ceiling panel is 25/32-1 in. Then tighten the nuts

above and below each suspension lug. The

full-size installation diagram can be used to help

adjust the height of the indoor unit.