Sanyo CHDZR14053, XMHX1252, XMHX1852 Installing the Ceiling Panel, Wiring the Ceiling Panel

Models: XMHX1852 CHDZR09053 XMHX1252 85464369098000 CHDZR14053

1 106
Download 106 pages 6.26 Kb
Page 38
Image 38

3-13-2. Installing the Ceiling Panel

The power must be turned ON in order to change the flap

angle. (Do not attempt to move the flap by hand. Doing so

Temporary latches

 

may damage the flap.)

XM

(1) Hang the temporary latches on the inside of the ceil-

 

ing panel to the receptacle on the unit to temporarily

Temporary latch

Refrigerant tubing joint

Fig. 3-44

attach the ceiling panel in place. (Fig. 3-44)

The ceiling panel must be installed in the correct direction

relative to the unit. Align the REF. PIPE and DRAIN marks

on the ceiling panel corner with the correct positions on the

unit.

(2) Align the panel installation holes and the unit screw

holes. (Fig. 3-45)

(3) Tighten the supplied washer head screws at the

4 panel installation locations so that the panel is

attached tightly to the unit.

(4) Check that the panel is attached tightly to the ceil-

ing. (Fig. 3-46)

At this time, make sure that there are no gaps between the

unit and the ceiling panel, or between the ceiling panel and

the ceiling surface.

If there is a gap between the panel and the ceiling, leave

the ceiling panel attached and make fine adjustments to

the installation height of the unit to eliminate the gap with

the ceiling.

CAUTION

Drainage check

Ceiling panel

REF. mark

DRAIN mark

Fig. 3-45

 

 

Panel installation hole

Washer head screws

(4 locations)

 

 

 

 

 

 

 

Do not

allow

 

Main unit

 

 

 

gaps

 

 

 

 

 

Fig. 3-46

 

 

 

 

 

 

Ceiling surface

Ceiling panel

If the screws are not sufficiently tight-

If a gap remains between the ceil-

 

ened, trouble such as that shown in

 

ing surface and the ceiling panel

 

the figure below may occur. Be sure to

 

even after the screws are tightened,

 

tighten the screws securely.

 

adjust the height of the unit again.

 

Ai

 

 

ge

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

r leaka

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air leakage from

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ceiling surface

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Staining

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Adjust so that there are no gaps.

Fig. 3-47

 

Condensation, water leakage

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3-13-3. Wiring the Ceiling Panel

(1)Open the cover of the electrical component box for control PCB.

(2)Connect the 7P wiring connector (red) from the ceil- ing panel to the connector on the control PCB in the

unit electrical component box. (Fig. 3-48)

If the connectors are not connected, the Auto flap will not operate. Be sure to connect them securely.

Check that the wiring connector is not caught between the electrical component box and the cover.

Check that the wiring connector is not caught between the unit and the ceiling panel.

(Direction that the unit faces has been changed to facilitate explanation.)

Electrical component box cover

Screws

(3 locations)

Fig. 3-48

Ceiling panel wiring connector

*Pass the wiring connector through the clamp to fasten it in place, as shown in the figure.

38

W-3WAY_ECO-i_US.indd 38

2008/02/07 10:55:53

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 38
Image 38
Sanyo CHDZR14053, XMHX1252, XMHX1852, CHDZR09053, 85464369098000 Installing the Ceiling Panel, Wiring the Ceiling Panel