HEAT PUMP TROUBLESHOOTING

HEAT PUMP TROUBLESHOOTING

Problem

Possible Cause

Action

 

 

Disconnect power to unit. Remove resistor

 

Heat anticipator (resistor) shorted

from t-stat bulb block. Plus in unit & allow to

 

(on applicable models)

operate. Feel resistor for heat. If not heat,

Room

 

replace resistor

temperature

Wide differential - partial loss of

Replace t-stat & check

uneven

t-stat bulb charge

 

(Heating cycle)

 

Refer to appropriate wiring diagram. Resistor

 

Incorrect wiring

is energized during “ON” cycle of compressor

 

 

or fan.

 

Defective thermistor or control board

Replace thermistor or electronic control board

 

 

 

Problem

Possible Cause

Action

 

Incorrect wiring

Refer to appropriate wiring diagram

 

Defrost control out of calibration

If outside coil temperature is 25°F or below,

 

& preselected time limit has elapsed, replace

 

(applicable models)

 

defrost control

 

 

Unit will not

 

If contacts remain closed between terminals

Defrost control contacts stuck

“2” & “3” of the defrost control after

defrost

preselected time interval has passed, replace

 

 

 

 

control

 

Defrost control bulb removed from

Reinstall & be assured that good bulb to coil

 

or not making good coil contact

contact is made

 

Outdoor coil thermistor

Replace thermistor or electronic control board

 

 

 

Problem

Possible Cause

Action

 

Dirty filter

Clean as recommended in Owner’s Manual

 

 

Check heat rise across coil. If unit operates

 

Unit undersized

efficiently, check if insulation can be added

 

to attic or walls. If insulation is adequate,

 

 

 

 

recommend additional unit or larger one

Does not heat

Outdoor t-stat open (applicable

T-stat should close at 38°F. Check continuity

of control. If temperature is below 38°F,

models)

adequately

replace control

 

 

Heater hi-limit control cycling on &

Check for adequate fan air across heater.

 

Check control for open at 160°F & close at

 

off

 

150°F

 

 

 

Shorted supplementary heater

Ohmmeter check, approx. 32-35 ohms

 

 

 

 

Incorrect wiring

Check applicable wiring diagram

 

 

 

 

Defective thermistor or electronic

Replace thermistor or electronic control board

 

control board

 

 