5) Ductwork Preparation
1) Duct ESP:
To determine your system's indoor external static pressure (ESP, in inches of water) use a duct calculator (as provided by your duct supplier). Include all flex duct transitions and discharge grille(s). If flex duct is used, be sure all the slack is pulled out of the flex duct. Flex duct ESP can increase considerably when not fully extended. DO NOT EXCEED a total of .30 ESP, as this is the MAXIMUM design limit for the
6) Chassis Installation
Install the following components as shown in Figure 5.
A.Ensure that the wall plenum is installed in accordance with the
B.Place the chassis into the closet with the outdoor side facing the wall plenum opening.
C.Slide the chassis into the wall plenum until the plenum divider seal is established. (See Figure 9)
2) Determining the Indoor CFM: Chart A – CFM
ESP (") | Capacity | |
|
|
|
BTU/h | 18000 | 12000 / 9000 |
.00 | 520 | 420 |
.10 | 510 | 410 |
|
|
|
.20 | 500 | 370 |
.30 | 490 | 330 |
3)Correct CFM (if needed): Chart B – Correction Multipliers
Correction Multipliers for:
230V | 1.00 |
208V | 0.97 |
|
|
Heating | 1.00 |
|
|
Cooling | 0.95 |
Figure 9
Slide-in View / Chassis Installation
The
11