3) Electrical Data

920-075-08

3) Electrical Data

Electrical Data

Model

V(E,H)A09K25V(E,H)A09K34V(E,H)09K50V(E,H)A12K25V(E,H)A12K34V(E,H,)A12K50V(E,H)A18K25V(E,H)A18K34V(E,H)A18K50

 

Voltage ( V)

230/208

230/208

230/208

230/208 230/208 230/208 230/208 230/208 230/208

LRA - Comp. (A)

21

21

21

24.0

24.0

24.0

47

47

47

Cooling Current (A)

4.4/4. 9

4.4/4. 9

4.4/4.9

5.5/6.1

5.5/6.1

5.5/6.1

9.2/10.2

9.2/10.2

9.2/10.2

MIN. Ckt. Amps (A)

15

20

30

15

20

30

15

20

30

Power Connection

HARD WIRED

HARD WIRED

HARD WIRED

Sample Nameplate (see your chassis nameplate)

FRIEDRICH AIR CONDITIONING CO.

 

WARNING

120524

MODEL NO 1

 

 

 

LISTED

SERIAL NO *

 

 

 

 

SAN ANTONIO, TEXAS

 

 

HEATING AND

 

 

VOLTS: 24,33,34

 

 

ELECTRICAL SHOCK AND
COOLING EQUIPMENT

VOLTAGE RANGE: 255-197

 

REFRIG CHARGE: 7 OZS. R22

 

 

 

MOVING PARTS HAZARD

APPLICABLE PATENTS:

DESIGN PRESSURE: 575 PSIG HS / 150 PSIG LS

COOLING: BTU/HR 8

 

CAN CAUSE INJURY OR

US 6,065,296

SEER: 10

COP: 16

 

NY MEA NO.: 295-00-E

HEAT PUMP BTU/HR: 14

 

DEATH

TOTAL COOLING AMPS: 9

 

USE ONE OF THE

TOTAL ELEC. HEAT AMPS: 15

 

PULL OUT DISCONNECT

FOLLOWING ITEMS

ELECTRIC HEAT WATTS: 18

 

FROM EACH CATEGORY

FOR PERMANENTLY CONNECTED UNITS ONLY:

HE D LOCATED ON THE

TO COMPLETE THE

COMP'. PLA 11 LRA 12

 

FRONT OF THIS UNIT TO

ASSEMBLY

MOTOR: FLA 13 HP 19

 

WALL PLENUM:

HEATER AMPS: 17

 

DIS BLE POWER BEFORE

MIN. CKT AMP ~0 USE ~1 MAX. TIME DELAY FU

VPAWP1 -8

 

 

 

SERVICING.

VPAWP1 -14

OR HACR TYPE CIRCUIT BREAKER.

 

SAMPLE

GENERAL UNIT INFORMATION:

 

OUTDOOR GRILLE

 

 

VPAL2

MAX OUTLET AIR TEMPERATURE: 2OO'F

 

 

INDOOR GRILLE

MAX EXTERNAL STATIC PRESSURE ELECTRIC

 

HEAT'..5 IN. WATER

 

 

VPRG1

"O" CLEARANCE TO COMBUSTIBLE MATERIAL

 

VPRG2

USE ON SINGLE OUTLET CIRCUIT ONLY

 

VPRG5

 

 

 

 

 

 

 

Important: all 208/230v chassis must be hard wired with properly sized breaker. See nameplate for specific chassis electrical requirements. See page 8 - Figure 5 for unit wiring and wall thermostat wiring. See page 8 for wire size. Use HACR type breakers to avoid nuisance trips. All field wiring must be done in accordance with nec and local codes.