SPECIFICATIONS
ELECTRICAL DATA
INDOOR UNIT | MW24C3G |
|
|
OUTDOOR UNIT | MR24C3G |
|
|
COOLING CAPACITY | 24,000 BTU, 7.03 kW |
|
|
POWER SOURCE | 208 / 230 V |
|
|
FREQUENCY | 60 Hz |
|
|
RUNNING CURRENT | 10.5 A |
|
|
INPUT WATTS | 2.4 kW |
|
|
E.E.R. | 10.0 BTU/hW, 2.93 kW/kW |
|
|
MOISTURE REMOVAL | 6.3 Pt/h, 3.0 L/hr |
|
|
AIR CIRCULATION HIGH | 659 cfm, 1,120 m3/hr |
|
|
MAXIMUM CURRENT | 11.5 A |
|
|
FAN MOTOR
POWER SOURCE | 230 V | ||
|
|
| |
| High | 1,480 r.p.m. | |
|
|
| |
INDOOR UNIT | Medium | 1,220 r.p.m. | |
|
| ||
Low | 1020 r.p.m. | ||
| |||
|
|
| |
| Quiet | 900 r.p.m. | |
|
|
| |
OUTDOOR UNIT | 1,100 r.p.m. | ||
|
|
|
NOISE LEVEL
|
| High | 48 dB | |
|
|
|
| |
INDOOR UNIT |
| Medium | 42 dB | |
|
|
| ||
Low | 37 dB | |||
|
| |||
|
|
|
| |
|
| Quiet | 33 dB | |
|
|
| ||
OUTDOOR UNIT | 56 dB | |||
|
|
|
|
COMPRESSOR AND REFRIGERANT
|
| Hermetic type, 4 pole, | |
TYPE |
| DC inverter motor, | |
|
| Scroll | |
DISCRIMINATION |
| ||
|
|
| |
WEIGHT (with oil) |
| 22 lbs, 10.0 kg | |
|
|
| |
REFRIGERANT TYPE | R410A | ||
|
|
| |
PRECHARGED REFRIGERANT | 2 lbs 14 oz, 1,300 g | ||
|
|
| |
Pipe length | 49 ft, 15 m | 2 lbs 14 oz, 1,300 g | |
|
|
| |
FULL CHARGE | 66 ft, 20 m | 3 lbs 1 oz, 1,400 g | |
|
| ||
82 ft, 25 m | 3 lbs 5 oz, 1,500 g | ||
| |||
|
|
| |
| 98 ft, 30 m | 3 lbs 8 oz, 1,600 g | |
|
|
| |
ADDITIONAL CHARGE | 0.21 oz/ft, 20 g/m | ||
|
|
| |
MAXIMUM HEIGHT DIFFERENCE | 66 ft, 20 m | ||
|
|
|
DIMENSIONS
INDOOR UNIT | H x W x D | |
|
| 320 x 998 x 228 mm |
OUTDOOR UNIT | H x W x D | |
|
| inch, 620 x 790 x 290 mm |
WEIGHT
INDOOR UNIT | Shipping / Net | 40 lbs | / 31 lbs | |
18 kg | / 14 kg | |||
|
| |||
|
|
|
| |
OUTDOOR UNIT | Shipping / Net | 97 lbs | / 88 lbs | |
44 kg | / 40 kg | |||
|
|
2010.11.02 | 1 |