6 F 3 B 0 3 5 6
1.4 Specifications
S20LP system specifications
Transmission cable | Silica glass SI 200/230μm |
| |
|
|
Cable connection | F07 connector |
(cable side connector) | (JIS C5976) |
|
|
Transmission distance | Max. 1 km (between stations) |
| Max. 4 km (between stations ; connecting SBR22) |
| Max. 30 km (system total) |
|
|
Topology | Loop |
|
|
Number of stations | Max. 64 stations |
|
|
Transmission speed | 2 Mbps |
|
|
Transmission code | Differential Manchester |
|
|
Modulation method | Baseband |
|
|
Communication service | (1) Scan transmission (cyclic broadcast) |
| (2) Message transmission (on request) |
|
|
S20LP-station specifications
|
| S20LP port for T2N | |
|
|
| |
Station type | PU245N...Optical fiber | SN325...Optical fiber | |
|
|
| |
Max. number on | 1 station | 2 stations (Note 1) | |
T2N/T3H |
| (Include of S20LP port) |
|
|
|
| |
|
|
|
|
Scan | transmission | 4096 words |
|
capacity |
| (Link register W (2048 words) in T2N/T3H is assigned) | |
|
| ||
|
|
|
|
Message | transmission |
| |
support |
|
| |
|
|
| |
|
| ||
|
| ||
RAS information | Station status, Online / Standby map (S20LP port / SN325) | ||
|
|
| |
Consumed current | S20LP port ... 1.5 [A] or less | SN325 ... 800 [mA] or less | |
(internal 5Vdc) |
|
| |
|
|
|
|
(Note 1) A T3H which has two