6 F 3 B 0 3 5 6

6)Response time limit

Designates a time used to limit the response time from the remote station in 0.1 second units.

F E

0

A+7

0:Use the user-specified value (0.1 to 3276.7 seconds)

1:Use the default value of 30 seconds.

This code indicates the type of register code in which the local or remote station transmission source data is stored. See “T-series Instruction Set (Ladder, SFC)” (UM-TS03***-E004).

RID

Meaning

 

RID

Meaning

 

 

 

 

 

 

*1

0000H

XW/YW registers

 

∗∗05H

F register (0 - 8191)

 

 

 

 

 

*2

0001H

W register

 

∗∗06H

F register (0 - 65535)

 

 

 

 

 

*3

0002H

LW register

 

0007H

T register

 

 

 

 

 

*3

0003H

RW register

 

0008H

C register

 

 

 

 

 

 

0004H

D register

 

0009H

SW register

 

 

 

 

 

 

 

*1 Includes the expansion F registers. One bank has 8k words (0 to 8191).

F 7 0

05H

Bank number ... 00H: T2N internal registers

F0000 to F1023

01H to 03H: Expansion F registers

F0000 to F8191

*2 Includes the expansion F registers(Only T3H). One bank has 64K words (0 to 65535).

F 7 0

06

Bank number ... 00H: T3H internal registers

F0000 to F32767

01H: Expansion F registers (IC card) F0000 to F65535

02H: Expansion F registers (IC card) F0000 to F57343

53