Diagnostic Error Messages

Diagnostic Error Messages

The controller runs background tests during normal operation. If a problem with the background tests occurs, an error message is shown (flashing) in the Display. These are called Diagnostic Error Messages (Table 3).

Table 3 - Diagnostic Error Messages

 

 

 

Display

Corrective Action

 

 

 

 

 

 

 

 

 

 

 

rPLC

1. Turn Blower Switch OFF for 2

 

 

 

Flashes on the display

minutes, then Turn Blower Switch

 

 

 

ON.

 

 

 

alternately with

 

 

 

 

 

 

 

 

temperature indicating

2. Replace the controller if the

 

 

 

that the controller’s

 

 

 

problem does not clear after repeating

 

 

 

internal diagnostics test

 

 

 

action 1 above three times.

 

 

 

has failed.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

rSET

1. Turn Blower Switch OFF for 2

 

 

 

 

 

 

 

 

 

Oven temperature has

 

 

 

 

 

 

 

minutes, then Turn Blower Switch

 

 

 

not reached at least

 

 

ON.

 

 

 

200˚F(93˚C) within 15

 

 

2. If problem does not clear, call

 

 

 

minutes of operation;

 

 

 

 

 

usually a result of the

 

 

the Middleby Cooking Systems

 

 

 

burner not lighting.

 

 

Group (MCSG) for assistance.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1. Check that the thermocouple is

 

 

 

 

 

 

connected to terminals 7 & 8 of the

 

 

 

 

 

 

temperature controller.

 

 

 

OPEn

2. If connections are good, then check

 

 

 

the continuity of the thermocouple at

 

 

 

 

 

 

 

 

 

Caused by an

room temperature. The resistance

 

 

 

open circuit in the

reading should be in the 9 - 20 Ohm

 

 

 

thermocouple circuit.

range. Remove & replace an open

 

 

 

 

 

 

thermocouple.

 

 

 

 

 

 

3. If the thermocouple checks good,

 

 

 

 

 

 

call MCSG for assistance.

 

 

 

 

 

 

 

 

 

 

r TC

1. Check the polarity of the

 

 

 

thermocouple leads; terminal 7 (-)

 

 

Reverse polarity of the

RED wire & terminal 8 (+) WHITE

 

 

thermocouple leads.

wire.

 

 

 

 

 

 

2. If polarity connections are

 

 

 

 

 

 

correct replace thermocouple.

 

 

 

 

 

 

 

 

Middleby Marshall Inc. • 1400 Toastmaster Drive • Elgin, IL 60120 • (847) 741-3300 • FAX (847) 741-4406

Middleby Corporation 24 Hour Service Hotline 1-800-238-8444

©1997 Middleby Marshall Inc.

Part # 36622

Page 11 of 11

P 9/97, Rev. B

Page 12
Image 12
Middleby Marshall KIT P/N 36939 manual rPLC, rSET, r TC, Diagnostic Error Messages, Display, Corrective Action, OPEn