Toshiba S20LP Self-diagnostic function, At initialization at power on, During operation

Models: S20LP

1 66
Download 66 pages 32.65 Kb
Page 34
Image 34

6 F 3 B 0 3 5 6

5.2 Self-diagnostic function

The S20LP-station has the following self-diagnostic function.

At initialization (at power on)

 

 

 

 

 

Diagnostic item

Station operation abnormal

 

 

 

 

ROM BCC check

Station moves into Down mode.

 

 

 

 

RAM read/write check

Communications with other stations are

 

 

 

 

CPU and peripheral LSI check

not possible. This state will be reset by

 

 

 

 

Station number check

power off/on (SN325, T2N) or pressing

 

 

Reset switch (SN325).

 

 

 

 

Transmission parameter

Station moves into Standby mode. In

 

(EEPROM) check

this state, scan transmission is not

 

possible but message transmission is

 

 

 

 

available. Station waits for transmission

 

 

parameter setting.

 

 

 

During operation

 

 

 

 

 

Diagnostic item

Station operation abnormal

 

 

 

 

Watch dog timer check

Station moves into Down mode.

 

 

 

 

Abnormal timer check

Communications with other stations are

 

(jabber timer) check

not possible. This state will be reset by

 

power off/on (SN325, T2N) or pressing

 

 

 

 

Reset switch (SN325).

 

 

 

 

Receive frame check (CRC check)

Station ignores the abnormal frame.

 

 

 

 

Response check

In message transmission, if response

 

 

from the target station cannot be

 

 

received, station re-sends the frame.

 

 

 

 

No signal state check

If no signal state continues more than

 

 

specified time, station starts re-

 

 

configuration operation.

 

 

 

33

Page 34
Image 34
Toshiba S20LP instruction manual Self-diagnostic function, At initialization at power on, During operation