6 F 3 B 0 3 5 6
5.2 Self-diagnostic function
The
∙ | At initialization (at power on) |
|
|
|
|
| Diagnostic item | Station operation abnormal |
|
|
|
| ROM BCC check | Station moves into Down mode. |
|
|
|
| RAM read/write check | Communications with other stations are |
|
|
|
| CPU and peripheral LSI check | not possible. This state will be reset by |
|
|
|
| Station number check | power off/on (SN325, T2N) or pressing |
|
| Reset switch (SN325). |
|
|
|
| Transmission parameter | Station moves into Standby mode. In |
| (EEPROM) check | this state, scan transmission is not |
| possible but message transmission is | |
|
| |
|
| available. Station waits for transmission |
|
| parameter setting. |
|
|
|
∙ | During operation |
|
|
|
|
| Diagnostic item | Station operation abnormal |
|
|
|
| Watch dog timer check | Station moves into Down mode. |
|
|
|
| Abnormal timer check | Communications with other stations are |
| (jabber timer) check | not possible. This state will be reset by |
| power off/on (SN325, T2N) or pressing | |
|
| |
|
| Reset switch (SN325). |
|
|
|
| Receive frame check (CRC check) | Station ignores the abnormal frame. |
|
|
|
| Response check | In message transmission, if response |
|
| from the target station cannot be |
|
| received, station |
|
|
|
| No signal state check | If no signal state continues more than |
|
| specified time, station starts re- |
|
| configuration operation. |
|
|
|
⎯ 33 ⎯