Friedrich H)A09K50L, R410A, H)A12K25L, H)A09K34L, H)A24K25L, H)A12K50L Chassis Specifications, Model

Models: H)A09K25L H)A12K50L H)A09K50L H)A24K10L H)A24K25L H)A24K34L H)A18K34L H)A12K34L H)A09K34L H)A24K75L H)A18K25L H)A24K50L H)A12K25L R410A

1 45
Download 45 pages 45.67 Kb
Page 8
Image 8

Chassis Specifications

Model 2010

VEA09K

VEA12K

VEA18K

VEA24K

COOLING DATA

 

 

 

 

COOLING BTUh

9400/9000

11500/11200

17000/16500

23000/22700

POWER (W)

959

1173

1888

2421

EER

9.8/9.8

9.8/9.8

9.0/9.0

9.5/9.5

SENSIBLE HEAT RATIO

0.74

0.72

0.70

0.70

HEAT PUMP DATA

 

 

 

 

HEATING BTUh

 

N/A

 

COP @ 47F

 

N/A

 

HEATING POWER (W)

 

N/A

 

HEATING CURRENT (A)

 

N/A

 

ELECTRICAL DATA

 

 

 

 

VOLTAGE (1 PHASE, 60 Hz)

230/208

230/208

230/208

230/208

VOLT RANGE

253-198

253-198

253-198

253-198

COOLING CURRENT (A)

4.2/4.4

5.2/5.4

8.1/8.5

10.0/10.4

AMPS L.R.

19.8

30

42

34.8

AMPS F.L.

3.5

4.5

7.8

9.5

INDOOR MOTOR (HP)

1/4

1/4

1/4

1/4

INDOOR MOTOR (A)

1.2

1.2

1.2

1.94

OUTDOOR MOTOR (HP)

 

N/A

 

1/4

OUTDOOR MOTOR (A)

 

N/A

 

0.85

AIRFLOW DATA

 

 

 

 

INDOOR CFM*

300

350

450

610

VENT CFM

60

60

60

60

MAX. ESP

.3"

.3"

.3"

.4"

PHYSICAL

 

 

 

 

DIMENSIONS (W x D x H)

23x23x32

23x23x32

23x23x32

23x23x47

NET WEIGHT (LBS)

114

124

144

167

SHIPPING WEIGHT (LBS)

125

135

155

220

R410A CHARGE (oz)

33.5

35.5

48

65

* Normal Value Wet Coil @ .1"ESP.

VHA09K

VHA12K

VHA18K

VHA24K

 

 

 

 

9200/9000

11500/11200

17000/16800

23000/22800

939

1186

1868

2527

9.8/9.8

9.7/9.7

9.1/9.1

9.1/9.1

0.74

0.72

0.70

0.70

 

 

 

 

8500

10800

16000

20000

3.0

3.0

3.0

3.0

830

1055

1563

1953

3.6

4.9

7.5

9.4

 

 

 

 

230/208

230/208

230/208

230/208

253-198

253-198

253-198

253-198

4.1/4.3

5.3/5.5

8.2/8.5

10.6/10.8

18.5

26

42

34.8

3.5

5

7.8

9.5

1/4

1/4

1/4

1/4

1.2

1.2

1.2

1.94

 

N/A

 

1/4

 

N/A

 

0.85

 

 

 

 

300

420

450

610

60

60

60

60

.3"

.3"

.3"

.4"

 

 

 

 

23x23x32

23x23x32

23x23x32

23x23x47

114

125

144

167

125

135

155

220

39

42

52

74

ELECTRIC HEAT DATA

 

 

 

 

 

 

 

 

 

 

VE/VHA09

 

 

VE/VHA12

 

 

 

HEATER WATTS

2500/2050

3400/2780

5000/4090

2500/2050

3400/2780

5000/4090

 

 

VOLTAGE

 

230/208

 

 

230/208

 

 

 

HEATING BTUh

8500/7000

11600/9500

17000/13900

8500/7000

11600/9500

17000/13900

 

 

HEATING CURRENT (AMPS)

10.9/9.9

14.8/13.4

21.7/19.7

10.9/9.9

14.8/13.4

21.7/19.7

 

 

MINIMUM CIRCUIT AMPACITY

15

19.9

28.6

15

19.9

28.6

 

 

BRANCH CIRCUIT FUSE (AMPS)

15

20

30

15

20

30

 

 

BASIC HEATER SIZE

2.5 Kw

3.4 Kw

5.0 Kw

2.5 Kw

3.4 Kw

5.0 Kw

 

 

 

 

 

 

 

 

 

 

 

ELECTRIC HEAT DATA

 

 

 

 

 

 

 

 

 

 

VE/VHA18

 

 

 

VE/VHA24

 

 

HEATER WATTS

2500/2050

3400/2780

5000/4090

2500/2050

3400/2780

5000/4090

7500/6135

10000/8180

VOLTAGE

 

230/208

 

 

 

230/208

 

 

HEATING BTUh

8500/7000

11600/9500

17000/13900

8500/7000

11600/9500

17000/13900

25598/2093934130/27918

HEATING CURRENT (AMPS)

10.9/9.9

14.8/13.4

21.7/19.7

10.9/9.9

14.8/13.4

21.7/19.7

32.6/29.5

43.5/39.3

MINIMUM CIRCUIT AMPACITY

15

19.9

28.6

17.2/15.9

22.1/20.3

30.7/28.1

44.3/40.3

57.9/52.7

BRANCH CIRCUIT FUSE (AMPS)

15

20

30

25

25

30

45

60

BASIC HEATER SIZE

2.5 Kw

3.4 Kw

5.0 Kw

2.5 Kw

3.4 Kw

5.0 Kw

7.5 Kw

10.0 Kw

6

Page 8
Image 8
Friedrich H)A09K50L, R410A, H)A12K25L, H)A09K34L, H)A24K25L, H)A12K50L, H)A12K34L, H)A24K10L Chassis Specifications, Model

H)A09K25L, H)A12K50L, H)A09K50L, H)A24K10L, H)A24K25L specifications

Friedrich R410A is a refrigerant blend that has become a cornerstone in the HVAC industry, particularly for air conditioning systems. This hydrofluorocarbon (HFC) is known for its efficiency and environmentally friendly properties, making it a popular alternative to older refrigerants like R22.

One of the main features of R410A is its exceptional thermal efficiency. It has a higher cooling capacity compared to R22, which allows for smaller and more efficient equipment. This efficiency translates to reduced energy consumption and lower operating costs for users. Additionally, the higher pressure capability of R410A enables the design of more compact systems, which is particularly beneficial for residential and commercial applications where space is often limited.

R410A is characterized by its zero ozone depletion potential (ODP), which is a significant advantage over its predecessors. This makes it a more environmentally responsible choice, aligning with global initiatives to phase out substances that harm the ozone layer. However, it is essential to note that while R410A does not deplete the ozone, it does have a global warming potential (GWP) of approximately 2,088, making it less favorable in terms of climate impact compared to natural refrigerants.

In terms of technology, R410A is typically utilized in systems that are designed specifically for this refrigerant. Equipment compatible with R410A often features advanced components that can handle the higher pressures required. Many modern air conditioning systems equipped with R410A also incorporate variable-speed compressors and advanced electronic controls, enhancing overall performance and comfort.

Additionally, R410A systems often come equipped with variable refrigerant flow (VRF) technology, which allows for precise temperature control in multiple zones of a building. This versatility makes R410A an ideal choice for both residential and commercial installations, providing optimal comfort throughout various spaces.

In summary, Friedrich R410A stands out due to its high energy efficiency, zero ozone depletion potential, and suitability for modern HVAC technologies. As the industry moves towards more sustainable practices, R410A serves as a reliable refrigerant that balances performance with environmental responsibility. It’s a significant choice for anyone looking to invest in efficient and eco-friendly heating and cooling solutions.