HEAT / COOL ROOM AIR CONDITIONERS: TROUBLESHOOTING TIPS

Problem

Possible Cause

Action

 

 

Disconnect power to unit. Remove resistor

 

Heat anticipator (resistor) shorted

from t-stat bulb block. Plus in unit & allow to

 

(on applicable models)

operate. Feel resistor for heat. If not heat,

Room temperature

 

replace resistor

uneven

Wide differential - partial loss of

Replace t-stat & check

(Heating cycle)

t-stat bulb charge

 

 

 

Refer to appropriate wiring diagram. Resistor

 

Incorrect wiring

is energized during "ON" cycle of compressor

 

 

or fan.

Problem

Possible Cause

Action

 

Incorrect wiring

Refer to appropriate wiring diagram

 

Defrost control timer motor not

Check for voltage at "TM" & "TM1" on timer. If

 

advancing (applicable models)

no voltage, replace control

 

Defrost control out of calibration

If outside coil temperature is 25F or below, &

 

preselected time limit has elapsed, replace

 

(applicable models)

Unit will not defrost

defrost control

 

 

If contacts remain closed between terminals

 

 

 

Defrost control contacts stuck

"2" & "3" of the defrost control after

 

preselected time interval has passed, replace

 

 

 

 

control

 

Defrost control bulb removed from

Reinstall & be assured that good bulb to coil

 

or not making good coil contact

contact is made

Problem

Possible Cause

Action

 

Exhaust or fresh air door open

Check if operating properly. Instruct customer

 

on proper use of control

 

 

 

Dirty fi lter

Clean as recommended in Owner's Manual

 

 

Check heat rise across coil. If unit operates

 

Unit undersized

effi ciently, check if insulation can be added

 

to attic or walls. If insulation is adequate,

 

 

Does not heat

 

recommend additional unit or larger one

 

T-stat should close at 38°F. Check continuity of

adequately

Outdoor t-stat open (applicable

control. If temperature is below 38°F, replace

 

models)

 

control

 

 

 

Heater hi-limit control cycling on &

Check for adequate fan air across heater.

 

Check control for open at 160°F & close at

 

off

 

150°F

 

 

 

Shorted supplementary heater

Ohmmeter check, approx. 32-35 ohms

 

Incorrect wiring

Check applicable wiring diagram

20