![](/images/new-backgrounds/1057736/577363x1.webp)
5.Drill two
1.587
2.375
2.625
3.275
III CHECK THERMOSTAT OPERATION
1.Fan Operation
A.Press fan button, starting fan operation. Fan icon turns on.
B.Press Fan button, stopping fan operation. Fan icon turns off.
2.Heating Operation
A.Press and Release MODE button until HEAT is dis- played.
B.Press up button until LCD readout reads 10 degrees above room temperature. Heating system should begin to operate within 5 minutes.
3.Cooling Operation
A.Press and Release MODE button until COOL is dis- played
B.Press down button until LCD readout reads 10 degrees below room temperature. Cooling system should begin to operate within 5 minutes.
6.Secure back plate to wall with 2 anchors and screws provid- ed making sure all wires extend through hole in back plate.
7.Connect wires to proper terminal of the connector block
8.Push any excess wire back into wall. Excess wire inside the thermostat plastic case can interfere with proper air flow across the temperature sensor. Seal hole in wall to prevent air leaks. Leaks can affect operation.
9.Install thermostat on back plate.
10.Turn on power to the unit.
On initial power up, the LCD readout will display oP.
WIRING DIAGRAMS
NOTE: All excess wire should be pushed back into the wall as far as possible. Excess wire inside the thermostat plastic case may interfere with the air flow across the temperature sensor.
SINGLE STAGE HEAT/COOL WIRING
Thermostat | Unit Terminal Strip |
IV. THERMOSTAT OPERATION
1.TEMPERATURE DISPLAY
The thermostat will display room temperature until the UP or DOWN button is pressed. The word SET appears when these buttons are pressed and the current set point is displayed. If no buttons are pressed for 5 seconds, the display will change back to show room temperature.
2.TIMEGUARD TIMER
A
3.CYCLE TIMER
In normal heating and cooling operation the thermostat will not allow more than 4 equipment cycles per hour (or 1 cycle every 15 minutes). Both the Y and W outputs have a
4.MINIMUM ON TIMER
HEAT | W | W |
COOL | Y | Y |
FAN | G | G |
24 VAC HOT | R | R |
24 VAC COMM | C | C |
Reversing Valve | B | B |
Connection to “B” terminal required on Heat Pump models
Once the equipment has turned on, it will remain on for a minimum of 3 minutes regardless of demand. However, the equipment can turn off in less than 3 minutes if a change in set point, or a change in mode occurs.
5.ERROR MESSAGES
E4 will be displayed if the thermostat has an internal memory failure. If E4 appears, replace the thermostat.
-- (two dashes) will be displayed if the temperature cannot properly read the room temperature. If - - appears, replace the thermostat.
2