the exhaust vent pipe must be listed for use with category III gas burning heaters such as "Saf-T-Vent" manufactured by Heat-Fab Inc. This vent system must be 100% sealed with a condensate trap located as close to the boiler as possible. When sizing exhaust piping and intake air piping, 90-degree elbows are equivalent to 10 feet (3.1 m) of straight pipe and 45-degree elbows are equal to 5 feet (1.5 m) of straight pipe.

The intake air piping can be PVC, CPVC, ABS, Galvanized steel or any suitable intake air piping that can be sealed. See Table 8 for Direct Vent Kit numbers.

TABLE 8: DIRECT VENT KITS.

HORIZONTAL DIRECT VENT KIT NO.

MODEL

211090

G(B,W) 1000

211090-1

G(B,W) 1300

211090-1

G(B,W) 1500

211090-4

G(B,W) 1850

211090-2

G(B,W) 2100

211090-3

G(B,W) 2500

VERTICAL DIRECT VENT KIT NO.

MODEL

211089

G(B,W) 1000

211089-1

G(B,W) 1300

211089-1

G(B,W) 1500

211089-4

G(B,W) 1850

211089-2

G(B,W) 2100

211089-3

G(B,W) 2500

AIR INTAKE TERMINAL

MODEL

191965-2

G(B/W) 1000

211336

G(B/W) 1300,1500,1850

211336-1

G(B/W) 2100, 2500

HORIZONTAL VENT INSTALLATION

This boiler can be vented through the rear of the cabinet with the use of the fluebox and vent adaptor. Any of the previous venting configurations can be installed with rear connections.

To change the unit to rear exhaust:

1.The vent collar and cover plates must be removed from the top and rear of the unit.

2.Trim the insulation from around the rear flue hole in the jacket and the fluebox. Support insulation from inside the fluebox to facilitate cutting. Use safety precautions such as gloves. Place the gasket and vent adaptor in the horizontal position. Place the gasket and flue plate in the vertical position as shown in Figure 4.

Figure 4. Switching from Vertical to Horizontal Venting.

POWER VENT (OPTIONAL)

The length of vent used in horizontally vented installations can be extended beyond the lengths shown in Tables 11 and 13 by implementing the kits listed below:

TABLE 9: POWER VENT KITS.

POWER VENT KIT NO.

MODEL

MAX. LENGTH

211499

G(B,W) 1000

110' (33.5 m)

211499-1

G(B,W) 1300

100' (30.5 m)

211499-1

G(B,W) 1500

100' (30.5 m)

211499-2

G(B,W) 1850

100' (30.5 m)

211499-3

G(B,W) 2100

100' (30.5 m)

211499-4

G(B,W) 2500

100' (30.5 m)

CONNECTING BOILER TO A COMMON VENT

Do not connect the boiler to a common vent or chimney with solid fuel burning equipment. This practice is prohibited by most local building codes as is the practice of venting gas fired equipment to the duct work of ventilation systems.

Where a separate vent connection is not available and the vent pipe from the boiler must be connected to a common vent with an oil burning furnace, the vent pipe should enter the common vent or chimney at a point ABOVE the flue pipe from the oil furnace.

UL/ULC listed double wall type B-1 gas vents, through 16" diameter, can be installed in heated and unheated areas and can pass through floors, ceilings, partitions, walls and roofs, provided the required clearance is observed.

At the time of removal of an existing boiler, the following steps shall be followed with each appliance remaining connected to the common venting system. Perform these steps while the other appliances remaining connected to the common venting system are not in operation.

1.Seal any unused opening in the common venting system.

2.Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or restriction, leakage, corrosion or other unsafe condition.

3.Insofar as is practical, close all building doors, windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any appliance not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers.

4.Test fire the appliance(s) being inspected, making sure to follow the manufacturers lighting and operating instructions. Appliance(s) operating controls should be adjusted to provide continuous service.

5.Check vent pressure of the appliance 24 inches (61.0 cm) above boiler vent collar. Vent pressure should be maintained between -0.02" W. C. and -0.04" W.C. to assure proper operation. For appliances with a draft hood, check for spillage with mirror, smoke or other device five minutes after placing appliance in operation.

6.After it has been determined that each appliance remaining connected to the common venting system properly vents when tested as outlined above, return doors, windows, exhaust fans,