STANDARD VENT - HORIZONTAL (CATEGORY III)

Figure 7.

TABLE 11. STANDARD HORIZONTAL VENTING (CATEGORY III)

 

APPLIANCE

CERTIFIED

EXHAUST

MAXIMUM

MODEL

CATEGORY

VENTING

VENT SIZE

VENT LENGTH

 

 

MATERIAL

INCHES (cm)

FEET (m)

I000

III

STAINLESS

10”(25.4 cm)

70' (21.3 m)

 

 

STEEL

 

 

1300

III

STAINLESS

12" (30.5 cm)

70' (21.3 m)

1500

STEEL

 

 

 

1850

III

STAINLESS

14"(35.6 cm)

35' (10.7 m)

2100

STEEL

 

 

 

2500

III

STAINLESS

16" (40.6 cm)

35' (10.7 m)

STEEL

 

 

 

 

WARNING: No substitutions of flue pipe or vent cap material are allowed. Such substitutions would jeopardize the safety and health of inhabitants.

A maximum of two elbows can be used on inlet and outlet vent piping respectively. Each elbow is equal to 10 feet (3 m) of straight pipe.

Use only special gas vent pipes listed for use with Category III gas burning heaters, such as stainless steel Saf-T-Vent by Heat Fab, Inc., available from A.O. Smith, 500 Tennessee Waltz Parkway, Ashland City, TN 37015 Phone: 1-800-433-2545 or Fax: 1-800-433-2515. Pipe joints must be positively sealed.

13

Page 13
Image 13
A.O. Smith 402, 400, 401, 403, 405, 404 instruction manual Standard Vent Horizontal Category, III Stainless, Steel, Iii