A.O. Smith 400, 402, 401, 403 Standard Vent Vertical Category, Type B or, Equivalent, 16 40.6 cm

Models: 405 403 404 402 400 401

1 48
Download 48 pages 6.6 Kb
Page 12
Image 12

STANDARD VENT - VERTICAL (CATEGORY I)

IMPORTANT!

VENT PRESSURE MUST BE MAINTAINED BETWEEN -0.02" W.C. AND -0.04" W.C. AT 24" (61.0 cm) ABOVE BOILER COLLAR.

Figure 6.

TABLE 10. STANDARD VERTICAL VENTING (CATEGORY I)

 

APPLIANCE

CERTIFIED

EXHAUST

MAXIMUM LENGTH

MODEL

CATEGORY

VENTING

VENT SIZE

WITHOUT BAROMETRIC DAMPER

 

 

MATERIAL

INCHES (cm)

FEET (m)

I000

I

TYPE B OR

10”(25.4 cm)

35 Feet (10.7 m) without damper

EQUIVALENT

 

*70 Feet (21.3 m) max. with damper

 

 

 

1300

I

TYPE B OR

 

35 Feet (10.7 m) without damper

1500

EQUIVALENT

12" (30.5 cm)

*70 Feet (21.3 m) max. with damper

 

1850

I

TYPE B OR

14"(35.6 cm)

35 Feet (10.7 m) without damper

2100

EQUIVALENT

 

*70 Feet (21.3 m) max. with damper

 

 

2500

I

TYPE B OR

16" (40.6 cm)

35 Feet (10.7 m) without damper

EQUIVALENT

 

*70 Feet (21.3 m) max. with damper

 

 

 

*Extending venting over 70 feet (21.3 m) may require special considerations.

Connection for the appliance exhaust vent to the stack must be as direct as possible. Maximum and minimum venting length for Category I appliances shall be determined per the latest edition of the National Fuel Code (U.S.) and CAN/CSA-B149.1 Installation Code (Canada).

The horizontal breaching of a vent must have an upward slope of not less than 1/4 inch per linear foot (2 cm/m) from the boiler to the vent terminal. The horizontal portion of the vent shall be supported to maintain clearances and to prevent physical damage or separation of joints.

12

Page 12
Image 12
A.O. Smith 400, 402, 401, 403, 405, 404 instruction manual Standard Vent Vertical Category, Type B or, Equivalent, 16 40.6 cm