ONE GENESIS (MODEL GW) HOT WATER SUPPLY BOILER WITH VERTICAL TANK

PRESSURE RELIEF VALVE RATING SHOULD NOT EXCEED PRESSURE CAPACITY OF ANY COMPONENT IN THE SYSTEM. PIPING SHOULD CONFORM TO LOCAL CODES.

BALL VALVES ARE SHOWN FOR SERVICING BOILER. HOWEVER, LOCAL CODES SHALL GOVERN THEIR USAGE.

IMPORTANT

WATER FLOW SWITCH PROTECTS THE BOILER IN CASE OF WATER SERVICE INTERRUPTION OR CIRCULATOR FAILURE.

PIPE TO OPEN DRAIN

XFACTORY INSTALLED ON UNIT == SUPPLIED WITH UNIT

= FIELD-INSTALLED

DANGER

TEMPERATURE SETTING SHOULD NOT EXCEED SAFE USE

TEMPERATURE AT FIXTURES. SEE WATER TEMPERATURE

CONTROL WARNING ON PAGE 26. IF HIGHER PREHEAT TEM-

PERATURES ARE NECESSARY TO OBTAIN ADEQUATE

BOOSTER OUTPUT, ADD AN ANTI-SCALD VALVE FOR HOT

WATER SUPPLIED TO FIXTURES.

INSTALL THERMAL EXPANSION TANK ON COLD WATER SUPPLY LINE, IF CHECK VALVE OR PRESSURE REDUCING VALVE IS USED IN SUPPLY.

 

MINIMUM

MODELS

PIPE SIZE

 

INCHES

GW-1000

 

THRU

2 1/2"

2500

NPT

 

 

FACTORY PUMP SIZING BASED

ON 50 EQUIVALENT FEET

(15.2 m) OF PIPE.

TWO TEMPERATURE WATER MIXING VALVE APPLICATION

Figure 13. Single boiler with vertical tank.

CIRCULATING RETURN

LINE CONNECTIONS

TEMPERED WATER LOOP, IF USED, CONNECT TO POINT R.

STORED TEMPERATURE WATER LOOP, IF USED, CONNECT TO ANY OPENING NEAR BOTTOM OF TANK.

20

Page 20
Image 20
A.O. Smith 401, 400, 402, 403, 405, 404 instruction manual Single boiler with vertical tank