Friedrich XQ08, XQ06, XQ05, XQ10, XQ12, YQ07, EQ08 Thru-the-wallinstallations, Figure D, Figure E

Models: EQ08 YQ07 XQ12 XQ10 XQ05 XQ08 XQ06

1 36
Download 36 pages 19.83 Kb
Page 8
Image 8
Figure D

920-197-00

STEP 6 Inspect the unit before inserting it into the sleeve. The fan and blower wheel should be manually rotated to insure that they turn freely. Be sure the electrical cord will be out of the way when inserting the unit into the sleeve.

NOTE: For your safety, DO NOT plug the electrical cord into an electrical outlet until installation is complete.

STEP 7 If the unit checks out OK, it is ready to be placed into position on bottom rails of the cabinet and pushed into place.

NOTE: Do all lifting of the unit by the bottom pan only and with assistance or help as necessary (see Figure A).

STEP 8 Install the white chassis seal gasket (item #6, page 6) and the gray window seal gasket (item #5). Carefully insert the white gasket (item #6) between the chassis and the cabinet starting at either bottom corner and go up the side, across the top and down the opposite side. Insert the gray gasket (item #5) between the window sashes as shown in Figure D. If chassis seal gasket is not installed, the operation of the unit will be negatively affected. Also, the operation noise and outside noise will be amplified.

STEP 9 Hold the decorative front as shown in Figure E. Insert the two tabs of the Decorative Front Panel into the slots in the top of the cabinet and lower the bottom of the decorative front to the bottom of the cabinet. Route the electrical cord to the right or left side of the bottom of the cabinet as required by the location of the electrical wall outlet. Use the notches provided at the bottom of the Decorative Front Panel for routing the electrical cord out of the unit. Attach the decorative front to the cabinet with two (2) No. 8 x ½" Phillips head screws (item #2, page 6).

STEP 10 CIRCUIT PROTECTION - If the air conditioner is circuit protected by a fuse, use a "TIME DELAY" fuse or HACR type Circuit Breaker due to momentary high current demand when your air conditioner is started. Before operating your unit, verify the ampere rating of the time-delay fuse or circuit breaker which protects your unit. The ampere rating of the time-delay fuse or circuit breaker shall be 15 amps. Refer to Operation section for more detailed operating instructions.

Figure D

GRAY FOAM GASKET (see illustration, item #5 on page 6)

CHASSIS SEAL GASKET

TO PREVENT AIR LEAKS AROUND THE AIR CONDITIONER, INSERT THE WHITE FOAM GASKET (item

# 6, page 6) BETWEEN THE AIR CONDITIONER AND THE CABINET.

Figure E

TAB SLOTS

TAB

LOCATIONS

NOTCHES PROVIDED

FOR ELECTRICAL

CORD EXIT

SCREW, #8 x ½" PHILLIPS HEAD (See ilustration, item # 2, page 6)

2 REQUIRED (1 EACH SIDE)

Thru-the-wall installations

STEP 1 After removing the unit from shipping carton, remove tape holding decorative front in place. Lay front in a safe out-of-the-way place, then slide chassis out of cabinet (see Figure A, page 7).

STEP 2 Remove the shell channel from the top of the cabinet (see Figure B, page 7).

NOTE: Not applicable to heat pump models sold without quick mounting cabinet.

STEP 3 LAYOUT - Cut and frame in an opening in the desired wall area using the illustration as a guide (see Figure F).

STEP 4 Place the cabinet in the framed opening.

NOTE: Measure and shim void spaces between the side of cabinet and wood framing before securing to wall.

STEP 5 Position the front edge to extend into the room 3/4" minimum at top of cabinet and 1" minimum at bottom (see Figure G).

STEP 6 Secure each side of the cabinet with No. 8 x ⅞" hex head screws

(item #3, page 6) or nails through the holes in the sides.

NOTE: ALTERNATE FASTENERS WHICH MAY BE USED FOR SECURING THE UNIT CABINET TO A WALL, INCLUDING MASONRY WALLS, ARE NOT FURNISHED (AVAILABLE AT LOCAL HARDWARE STORES).

MOLLY OR TOGGLE BOLT

EXPANSION ANCHOR BOLT

8

Page 8
Image 8
Friedrich XQ08, XQ06, XQ05, XQ10, XQ12, YQ07, EQ08 operation manual Thru-the-wallinstallations, Figure D, Figure E