4
InstallationInstallation
InstallationInstallation
Installation FOR RESIDENTIAL USE ONLYFOR RESIDENTIAL USE ONLY
FOR RESIDENTIAL USE ONLYFOR RESIDENTIAL USE ONLY
FOR RESIDENTIAL USE ONLY
NOT TO BE INSTALLED OVER GAS GRILLSNOT TO BE INSTALLED OVER GAS GRILLS
NOT TO BE INSTALLED OVER GAS GRILLSNOT TO BE INSTALLED OVER GAS GRILLS
NOT TO BE INSTALLED OVER GAS GRILLS
PLEASE READ ENTIRE INSTRUCTIONS BEFORE PROCEEDING.PLEASE READ ENTIRE INSTRUCTIONS BEFORE PROCEEDING.
PLEASE READ ENTIRE INSTRUCTIONS BEFORE PROCEEDING.PLEASE READ ENTIRE INSTRUCTIONS BEFORE PROCEEDING.
PLEASE READ ENTIRE INSTRUCTIONS BEFORE PROCEEDING.
INSTALLATION MUST COMPLY WITH ALL LOCAL CODES.INSTALLATION MUST COMPLY WITH ALL LOCAL CODES.
INSTALLATION MUST COMPLY WITH ALL LOCAL CODES.INSTALLATION MUST COMPLY WITH ALL LOCAL CODES.
INSTALLATION MUST COMPLY WITH ALL LOCAL CODES.
IMPORTANT:IMPORTANT:
IMPORTANT:IMPORTANT:
IMPORTANT: Save these Instructions for the Local Electrical Inspector’s use.
INSTALLER:INSTALLER:
INSTALLER:INSTALLER:
INSTALLER: Please leave these Instructions with this unit for the owner.
OWNER:OWNER:
OWNER:OWNER:
OWNER: Please retain these instructions for future reference.
Safety Warning: Turn off power circuit at the service entrance and lock out
panel, before wiring this appliance.
Requirement: 120 V AC, 60 Hz. 15 or 20 A

Weight: 30” Model 34 lbs - 36” Model 38,5 lbs

Diameter of Transition 4” 3/4
Diameter of exhaust Duct required 4” 3/4

Considerations before installing HoodConsiderations before installing Hood

Considerations before installing HoodConsiderations before installing Hood

Considerations before installing Hood

1. For the most efficient air flow exhaust, use a straight run or as few elbows
as possible.
CAUTION:CAUTION:
CAUTION:CAUTION:
CAUTION: Vent unit to outside of building, only.
2. If allowed in your area, use metallic flex ducting only to connect rigid duct
directly to transitions.
3. COLD WEATHER installations should have an additional backdraft damper
installed to minimize backward cold air flow and a nonmetallic thermal
break to minimize conduction of outside temperatures as part of the
ductwork. The damper should be on the cold air side of the thermal break.
The break should be as close as possible to where the ducting enters the
heated portion of the house.
4. Hood installation height above cooktop is the users preference. The lower
the hood above the cooktop, the more efficient the capturing of cooking
odors, grease and smoke. We recommends the hood be installed 18,5”
minimum above an electric cooktop or 25,6” minimum above a gas
cooktop . Be sure that your hood model fits your installation.