1.PREPARATION STEPS

1.PREPARATION STEPS

A.Calibrate and Check Operation of Measuring Equipment Follow manufacturer’s recommended procedures for calibration and equipment check out.

B.Prepare Heating Unit for Testing Drill two 1/4 inch holes in the flue between the heating plant and the barometric draft regulator. If space permits, the holes should be located in a straight section of the flue, at least two flue diameters from the elbow in the flue pipe and at least one diameter from the draft regulator. The purpose of the two holes in the flue pipe is to speed up testing and reduce instrument handling.

C.Clean and Seal Heating Plant Make sure the burner blast tube, fan housing, and blower wheel are clear of dirt and lint. Seal any air leaks into the combustion chamber.

D.Nozzle Inspection Annual replacement of nozzle is recommended. The nozzle size should match the design load. DO NOT OVERSIZE. (Determination of oversizing can be determined prior to your adjustment. If the firing rate should be reduced refer to Table 4.) Short cycles and low percent “on” time result in higher overall pollutant emissions and lower thermal efficiency. An in-line oil filter will reduce service problems due to nozzle clogging.

The filter should be located as close as possible to the oil burner. Care should be taken to prevent air leakage in the oil suction line. Use continuous runs of copper tubing and use minimum number of joints and fittings. Always use flare fittings.

E.Adjustment of Electrodes Adjust ignition electrodes as specified in Figure 10.

F.Operate Burner Operate burner, adjust air setting for good flame by visual observation, and run for at least 10 minutes or until operation has stabilized.

G.Check Burner Pressure Bleed air from pump and nozzle piping. Check pump pressure and adjust to nameplate pump pressure, if necessary.

2.COMBUSTION ADJUSTMENT STEPS

H.Set Draft Check the draft reading over the fire with a draft gauge through a hole in the inspection door. The hole is above the flame level. Adjust the barometric draft regulator on the flue to give the over fire of -.02" W.C.

I.Check Smoke Readings After burner has been operating 5 or 10 minutes, take a smoke

measurement in the flue, following the smoke tester instructions. Oily or yellow smoke spots on the filter paper are usually a sign of unburned fuel, indicating very poor combustion (and likely high emissions of carbon monoxide and unburned hydrocarbons). This condition can sometimes be caused by too much air, or by other factors. If this condition cannot be corrected, major renovation or even burner replacement may be necessary.

J.Develop Smoke - CO2 Curve Record

measurements of smoke and CO2 from the flue. Then establish the smoke - CO2 curve by taking readings over a range of air settings, as shown in Figure 8.

To do this, start with the air gate set at nearly

full open and then take smoke and CO2 readings at progressively lower air settings, as necessary to visualize the general shape of the

curve. (The CO2 readings will increase as the air setting is decreased, unless combustion is incomplete.) Do not set the air gate to give a smoke reading above No. 4 or No. 5. Plot the points on graph paper, as in Figure 8. Usually 3 or 4 readings are enough to establish the curve.

In adjusting each air setting, it is helpful to note the various positions of air gate at which measurements are made so that the final setting can be located quickly.

K.Adjust Air Setting Examine the smoke - CO2 plot and, keeping in mind the curve of Figure 6, note the location of the “knee” where the smoke number begins to rise sharply. Noting the air gate position marks, adjust the air setting to a

CO2 level 1/2 to 1 percent lower than the CO2 level at the “knee”. (This provides a tolerance against possible shifts in the setting over a period of time.) Do not increase the air setting any more than necessary on the lower portion of the curve below the “knee”.

The characteristic curve for some burners may not yield a distinct “knee” in the curve. In such cases, the setting should be made near the minimum smoke, (using judgement).

Lock the air adjustment and repeat draft,

CO2 and smoke measurements to make sure the setting has not shifted.

3.COMBUSTION DIAGNOSIS

L.Check Performance A well-matched and well-tuned burner should be capable of operation with smoke not greater than No. 2 and at a CO2 level not less than 10%.

If this cannot be reached, check the following:

Manual

2100-422M

Page

20 of 42