TABLE A

RESET BUTTON OPERATION

If the burner is in the

 

Pushing the Reset button will:

 

 

 

Button Click

Button Hold

Button Hold

below state:

 

(press < 1 second)

(press > 1 second)

(press 15+ seconds)

Lockout

Reset from Soft Lockout

 

Reset from Restricted (Hard) Lockout

 

 

 

 

Valve-on Delay,

Go to Pump Prime

 

 

Trial for Ignition,

Disable the Burner:

 

(see Below)

Enables Pump Priming:

Ignition Carryover

 

Any time the burner is running,

 

 

After the reset button has been held for

 

Yellow LED flashes to

press and hold the reset button

 

15 seconds, the button can then be

 

indicate cad cell resistance.

to disable the burner.

tapped during the next ignition sequence

 

The burner will remain off as

Run (igniter is shut off)

See "Cad Cell Resistance

to enter Pump Prime mode.

long as the button is held.

 

Indicator" for table of

 

 

 

 

 

resistance values.

 

 

 

 

 

 

Motor-Off Delay, Standby

No action

 

 

 

 

 

 

Pump Prime

No action

Exit Pump Prime mode and return to Standby

 

 

 

 

TABLE B

STATUS LIGHTS

LED

On Continuously

Flashing

Color

 

 

 

 

 

Red

Restricted (hard) Lockout

Soft Lockout

Green

Flame Detected (Could be flame or stray light)

Recycle

Yellow

Control is in Pump Prime mode or

Cad Cell resistance. See "Cad Cell Resistance Indicator"

Reset button currently held for 15+ seconds

section for table of resistance values.

 

 

 

 

Manual

2100-422M

Page

15 of 42

Page 15
Image 15