Bard FLR110D60F, FLR140D60F, FLR110D48F, FLR085D36F Figure Appliances Located In Confined Spaces

Models: FH110D60F FLR085D36F FC085D36F FLF085D36F FLF110D48F FLR110D60F FLF110D60F FLR110D48F FH085D36F FH110D48F FLR140D60F

1 42
Download 42 pages 59.71 Kb
Page 29
Image 29
Manual background

FIGURE 14

APPLIANCES LOCATED IN CONFINED SPACES

ALL AIR FROM OUTDOORS THROUGH VENTILATED ATTIC

NOTE: The inlet and outlet air openings shall each have a free area of not less than one square inch per 4,000 BTU per hour (35 square inches per gallon per hour) of the total input rating of all appliances in the enclosure.

FIGURE 15

APPLIANCES LOCATED IN CONFINED SPACES

ALL AIR FROM OUTDOORS

INLET AIR FROM VENTILATED CRAWL SPACE AND OUTLET AIR TO VENTILATED ATTIC

NOTE: The inlet and outlet air openings shall each have a free area of not less than one square inch per 4,000 BTU per hour (35 square inches per gallon per hour) of the total input rating of appliances in the enclosure.