Fujitsu Siemens Computers Siemens S7 300 manual HMI Factory Setting, Connection, IWn, IDn, QWn

Models: Siemens S7 300

1 6
Download 6 pages 20.4 Kb
Page 1
Image 1

Series HMI Connection Manual

Siemens S7 300 (ISO TCP)

HMI Factory Setting:

IP Address: 192.168.0.1

COM Port: 102

Control Area / Status Area: DBW0 / DBW20

Connection

Standard Jumper Cable / Network Cable without jumper (Auto-detected by HMI)

Definition of PLC Read/Write Address a. Registers

 

Format

 

 

 

Type

Word No.(n)

Read/Write Range

Data Length

Note

 

Bank No.(m)

 

 

 

Input Image

IWn

IW0 – IW65534

Word

 

IDn

ID0 – ID65532

Double Word

 

 

 

Output Image

QWn

QW0 – QW65534

Word

 

QDn

QD0 – QD65532

Double Word

 

 

 

Internal Bits

MWn

MW0 – MW65534

Word

 

MDn

MD0 – MD65532

Double Word

 

 

 

 

DBm.DBWn

DB1.DBW0 –

Word

1

Data Area

 

DB255.DBW65534

 

 

DBm.DBDn

DB1.DBD0 –

Double Word

1

 

 

 

DB255.DBW65532

 

 

 

DBWn

DBW0 – DBW65534

Word

 

Data Area (DB10)

DBDn

DBD0 – DBD65532

Double Word

 

VWn

VW0 – VW65534

Word

 

 

 

 

VDn

VD0 – VD65532

Double Word

 

Timer

Tn

T0 – T65535

Word

2

Counter

Cn

C0 – C65535

Double Word

3

V1.02 Revision January, 2012

203

Page 1
Image 1