LEAK TESTING HEATER GAS CONNECTIONS:

LEAK TESTING HEATER GAS CONNECTIONS:

1.Open manual shutoff valve.

2.Open main gas valve located near gas meter.

3.Make sure control knob of heater is in the OFF position.

4.Check all joints from manual gas valve up to gas control and including the manifold assembly. Apply the soap solution around the connections, valve and tubing. Soap bubbles will appear where a leak is present.

5.If a leak is present, immediately turn off gas supply, tighten any leaky fittings, turn gas on and recheck.

6.To check burner and safety valve, the burner must be lit (See operating Instructions.). Check the rest of the connections for leaks.

7.Turn off the heater (See Instructions.).

Manual

Shutoff

Valve

Open

Closed

Manual Shutoff Valve

Combination

OPERATING HEATER:Manual backgroundManual backgroundManual background Gas Control Location

Manual

Shutoff

Valve

Checking Gas Joints

NOTE:

Never use an open flame to check for a leak. Apply a mixture of liquid soap and water to all joints. Bubbles forming show a leak. Correct all leaks at once.

OPERATING HEATER:

WARNING:

Before lighting, smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor. If you smell gas, follow the Safety Instructions on the front page and under Section I.